9 Troubleshooting and Maintenance
Event code
Event name
34C20000 hex
Slave I/O
Refresh Error
34C30000 hex
Slave User
Allocation
Area Setting
Failed
64AC 0000 hex
Send Time-
out Error
74600000 hex
Master Func-
tion
Enable/Dis-
able Failed
74610000 hex
Master Fixed
Allocation
Area Setting
Failed
9-38
Meaning
Assumed cause
The I/O memory in
• I/O words are allocated in an
the destination
EM bank that does not exist.
CPU Unit for I/O
refreshing could not
be found when
refreshing the slave
function data in the
CPU Unit.
An error occurred in
• The slave function is not dis-
the following opera-
abled.
tion for user alloca-
• There is a mistake in the user
tion of the slave.
allocations to a slave.
• CPU Unit is not in PROGRAM
mode.
• More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
A send timeout
• There is no slave or other
occurred.
device on the network.
• The same baud rate is not set
for all nodes.
• Communications cable lengths
(trunk line and branch lines) are
unsuitable.
• A communications cable is dis-
connected or loose.
• The terminating resistance is
somewhere other than the ends
of the trunk line.
• Noise
• There is an error in the CAN
controller.
An operating error
• An attempt was made to enable
occurred when
the master function when it was
enabling or dis-
already enabled.
abling the master
• An attempt was made to dis-
function.
able the master function when it
was already disabled.
• CPU Unit is not in PROGRAM
mode.
• More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
An error occurred in
• The master function is not
one of the following
enabled.
operations for fixed
• The scan list is not disabled.
allocation of the
• CPU Unit is not in PROGRAM
master.
mode.
• More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
Level
Maj
Prt
Min
Obs Info
S
page 9-48
S
page 9-48
S
page 9-49
S
page 9-50
S
page 9-51
Reference