Lenovo NeXtScale nx360 M5 Installation And Service Manual page 450

Machine type 5465
Hide thumbs Also See for NeXtScale nx360 M5:
Table of Contents

Advertisement

CIM Information
Prefix: PLAT ID: 0168
User Response
1. Run the hard disk drive diagnostic test on drive n.
2. Reseat the following components: a. Hard disk drive (wait 1 minute or more before reinstalling
the drive) b. Cable from the system board to the backplane
3. Replace the following components one at a time, in the order shown, restarting the server
each time: a. Hard disk drive b. Cable from the system board to the backplane c. Hard disk
drive backplane (n = hard disk drive number)
806f020d-0419ffff : Failure Predicted on drive [StorageVolumeElementName] for array
[ComputerSystemElementName]. (SDHV Drive 10)
This message is for the use case when an implementation has detected an Array Failure is Predicted.
May also be shown as 806f020d0419ffff or 0x806f020d0419ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
Yes
Alert Category
System - Predicted Failure
SNMP Trap ID
27
CIM Information
Prefix: PLAT ID: 0168
User Response
1. Run the hard disk drive diagnostic test on drive n.
2. Reseat the following components: a. Hard disk drive (wait 1 minute or more before reinstalling
the drive) b. Cable from the system board to the backplane
3. Replace the following components one at a time, in the order shown, restarting the server
each time: a. Hard disk drive b. Cable from the system board to the backplane c. Hard disk
drive backplane (n = hard disk drive number)
806f020d-041affff : Failure Predicted on drive [StorageVolumeElementName] for array
[ComputerSystemElementName]. (SDHV Drive 11)
This message is for the use case when an implementation has detected an Array Failure is Predicted.
May also be shown as 806f020d041affff or 0x806f020d041affff
436
Lenovo NeXtScale nx360 M5 Installation and Service Guide