Addr.
Setting Title
3510
REP. CHAR. 2
3511
T-HOLDING
3512
T-SIGNAL

2.18.2.2 Information for the Out-of-Step Protection

F.No.
Alarm
05053 >BLOCK O/S
05061 O/S OFF
05062 O/S BLOCKED
05063 O/S ACTIVE
05067 O/S char. 1
05068 O/S char. 2
05069 O/S det. char.1
05070 O/S det. char.2
05071 O/S TRIP char.1
05072 O/S TRIP char.2
7UM62 Manual
C53000-G1176-C149-3
Setting Options
1..8
0.20..60.00 sec
0.02..0.15 sec
>BLOCK out-of-step protection
Out-of-step protection is switched OFF
Out-of-step protection is BLOCKED
Out-of-step protection is ACTIVE
Out-of-step pulse of characteristic 1
Out-of-step pulse of characteristic 2
Out-of-step characteristic 1 picked up
Out-of-step characteristic 2 picked up
Out-of-step TRIP characteristic 1
Out-of-step TRIP characteristic 2
Out-of-Step Protection (ANSI 78)
Default Setting
4
Number of Power Swing: Cha-
racteristic 2
20.00 sec
Holding Time of Fault Detection
0.05 sec
Min. Signal Time for Annun.
Char. 1/2
Comments
Comments
147