Siemens SINAMICS G120 Operating Instructions Manual page 279

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 11- 1
EMC
Phenomenon
Conducted
emissions
(disturbance
voltage)
Radiated
emissions
Harmonic Currents
Table 11- 2
Typical Harmonic Current (% of rated input current) at U
Note
Units installed within the category C2 (domestic) environment require supply authority
acceptance for connection to the public low-voltage power supply network. Please contact
your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Conducted disturbance voltage and radiated emissions
Inverter type
Remark
All inverters with integrated class A filters.
Order number:
6SL3210-1KE**-*A*0
Inverter frame sizes A and B with integrated class A filter.
Order number:
6SL3210-1KE1*-*A*0
6SL3210-1KE21-*A*0
In a domestic environment this product may cause radio
interference in which case supplementary mitigation
measures may be required.
Inverter frame size C with integrated class A filter.
Order number:
6SL3210-1KE22-*A*0
6SL3210-1KE23-*A*0
This type of PDS is not intended to be used in low-voltage
public power supply network which supplies domestic
premises. Radio frequency interference is expected if used
on such a network.
Harmonic Currents
5th
7th
54
39
11th
13th
11
5
11.4 Electromagnetic Compatibility
1 %
K
17th
19th
5
3
Technical data
Level acc. to
IEC 61800-3
Category C2
First Environment -
Professional Use
Category C2
First Environment -
Professional Use
Category C3
Second
Environment
23rd
25th
2
2
277