If you wish to transfer the parameter setting from the inverter on to a memory card (Upload),
you have two options:
Automatic upload
The inverter power supply has been switched off.
1. Insert an empty memory card into the inverter.
2. Then switch-on the inverter power supply again.
After it has been switched-on, the inverter copies the
modified parameters to the memory card
NOTICE
If the memory card is not empty and already contains a parameter setting, the inverter will
take on the parameter setting from the memory card. The previous setting in the inverter
will be deleted.
Manual upload
If you do not wish to switch off the inverter power supply or
you do not have an empty memory card available, you will
need to transfer the parameter setting to the memory card
as follows:
1. The inverter power supply has been switched on.
2. Insert a memory card into the inverter.
STARTER
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Start the data transfer with p0971 = 1.
Check the value of parameter p0971.
If data transfer has been completed, then the
inverter sets p0971 to 0.
5.6 Data backup and series commissioning
Transfer the setting to the
empty memory card
BOP-2
Start data transfer in the menu "OPTIONS" -
"TO CRD".
Wait until the BOP-2 signals that data transfer
has been completed.
Commissioning
73