5.5.5

Making additional settings

After the basic commissioning, you can adapt the inverter to your application as described in
the Commissioning (Page 47).
STARTER offers two options:
1. Change the settings using the appropriate screen forms - our recommendation.
2. You change the settings using the parameters in the expert list.
Saving settings so that they are not lost when the power fails
All of the changes that you make are temporarily saved in the inverter and are lost the next
time the power supply is switched off. For your changes to be permanently saved in the
inverter, you must save the changes using the
the button, you need to mark the appropriate drive in the project navigator.
Go offline
You can now exit the online connection after the data backup (RAM to ROM) with
"Disconnect from target system".
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Navigation bar: For each inverter function, select the corresponding screen form.
tabs: Switch between screen forms.
If you change the settings using screen forms you do not need to know the parameter
numbers.
If you wish to change the settings using the expert list, you need to know the
corresponding parameter number and its significance.
5.5 Commissioning with STARTER
button (RAM to ROM). Before you press
Commissioning
67