Technical data
11.8 Accessories
11.8
Accessories
11.8.1
Line reactor
The major electrical specification of the line reactors is the same as for the suitable inverter.
This applies to:
● line voltage
● line frequency
● rated current
The admissible ambient conditions of the line reactors are the same as for the suitable
inverter. This applies to:
● storage and transport temperature
● operating temperature
● relative humidity
● shock and vibration load
Table 11- 10 Technical specifications of the line reactors
Feature
MLFB
MLFB of the suitable
inverter
Inductance
Power loss at 50/60 Hz
Cable cross section
Tightening torque
PE connection
Degree of protection
Overall dimensions
Width
Height
Depth
Fixing dimensions
Width
Height
Fixing screw
Weight
286
0.55 kW ... 1.1 kW
6SL3203-0CE13-2AA0
6SL3210-1KE11-8 ⃞ ⃞ 0
6SL3210-1KE12-3 ⃞ ⃞ 0
6SL3210-1KE13-2 ⃞ ⃞ 0
2.5 mH
25 W
2.5 mm
/ 14 AWG
2
0.6 Nm ... 0.8 Nm
5 lbf in ... 7 lbf in
M4 (3 Nm / 26.5 lbf in)
IP20
125 mm
120 mm
71 mm
100 mm
55 mm
4 × M5 (6 Nm)
1.1 kg
Suitable for inverter with rated power of
1.5 kW ... 4.0 kW
FSA
6SL3203-0CE21-0AA0
6SL3210-1KE14-3 ⃞ ⃞ 0
6SL3210-1KE15-8 ⃞ ⃞ 0
6SL3210-1KE17-5 ⃞ ⃞ 0
6SL3210-1KE18-8 ⃞ ⃞ 0
1 mH
40 W
2.5 mm
/ 14 AWG
2
0.6 Nm ... 0.8 Nm
5 lbf in ... 7 lbf in
M4 (3 Nm / 26.5 lbf in)
IP20
125 mm
140 mm
71 mm
100 mm
55 mm
4 × M5 (6 Nm)
2.1 kg
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
5.5 kW ... 7.5 kW
FSB
6SL3203-0CE21-8AA0
6SL3210-1KE21-3 ⃞ ⃞ 0
6SL3210-1KE21-7 ⃞ ⃞ 0
0.5 mH
55 W
6.0 mm
/ 10 AWG
2
1.5 Nm ... 1.8 Nm
13 lbf in ... 16 lbf in
M5 (5 Nm / 44 lbf in)
IP20
125 mm
145 mm
90 mm
100 mm
65 mm
4 × M5 (6 Nm)
2.95 kg
SINAMICS G120C Inverter