Interconnecting the motorized potentiometer with the setpoint source
You have two options for interconnecting the motorized potentiometer with the setpoint
source:
1. Using p0015, select a configuration that is suitable for your application.
2. Interconnect the main setpoint with the motorized potentiometer by setting p1070 to
Example of parameterization of the motorized potentiometer
Table 8- 15
Parameter
p0015 = 9
p1040 = 10
p1047 = 5
p1048 = 5
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Please refer to the section titled Selecting the interface assignments (Page 41) to find out
which configurations are available for your inverter.
1050.
Implementing a motorized potentiometer using digital inputs
Description
Macro drive unit: Configure inverter on MOP as the setpoint source
The motor is switched on and off via digital input 0.
The MOP setpoint is increased via digital input 1.
The MOP setpoint is decreased via digital input 2.
MOP start value
Each time the motor is switched on a setpoint corresponding to 10 rpm is specified
MOP ramp-up time:
The MOP setpoint is increased from zero to maximum (p1082) in 5 seconds
MOP ramp-down time:
The MOP setpoint is reduced from maximum (p1082) to zero in 5 seconds
Functions
8.4 Setpoint sources
175