Table 11- 6
G120C Frame Sizes A, 3 AC 380 V ... 480 V, ± 10 % - part 3
6SL3210-...
Order No.
Filtered, IP20
Unfiltered, IP20
Rated / Low Overlaod values
Rated / LO power
Rated / LO input current
Rated / LO Output current
High Overload values
HO power
HO input current
HO output current
Power losses, filtered
Power losses, unfiltered
Fuse according to IEC
Fuse according to UL
Required cooling air flow
Cross section of line and motor cable
Tightening torque for line and motor cable
Weight, filtered
Weight, unfiltered
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
... 1KE18-8U*0
... 1KE18-8A*0
4.0 kW
11.4 A
8.8 A
3.0 kW
10.6 A
7.3 A
0.146 kW
0.141 kW
3NA3 805 (16 A)
15 A class J
5 l/s
1.5 ... 2.5 mm
2
16 ... 14 AWG
0.5 Nm
4.4 lbf in
1.9 kg
1.7 kg