4 Technical Data
4.1.3

Binary Inputs and Outputs

Binary inputs
Number
Rated Voltage Range
Pick-up threshold
- For nominal voltages
- For nominal voltages
- For nominal voltages
Current consumption, energized
Maximum Permissible Voltage
Impulse filter on input
Binary Outputs
Signalling/Trip Relays (see also terminal assignments in Appendix A.2))
Number and information
UL Listed
x
Switching capability MAKE
Switching capability OFF
Switching voltage
DC
AC
Admissible current per contact (continu-
ous)
Permissible current per contact
(close and hold)
Permissible total current
on common path contacts
Permissible relative closing time
Operating time, approx.
1
Alarm relay
)
Switching capacity
Switching voltage
Permissible Current per Contact
322
7 (configurable)
24 VDC to 250 VDC, in 3 ranges, bipolar
Changeable via jumpers
24/48 VDC and 60/110/125 VDC
110/125/220/250 VDC
220/250 VDC
approx. 1.8 mA
Independent of the control voltage
300 VDC
220 nF coupling capacitance at 220 V with recovery time > 60 ms
NO Contact (nor-
1
mal)
)
5
8 ms
With 1 NC contact or 1 NO contact (switchable)
MAKE 1000 W/VA
OPEN 30 VA
40 W ohmic
25 VA at L/R ≤ 50 ms
250 V
5 A continuous
30 A for 0.5 s
U
high
U
low
U
high
U
low
U
high
U
low
(allocatable)
1
NO Contact (fast)
)
-
1000 W/VA
30 VA
40 W ohmic
25 W/VA for L/R ≤ 50ms
250 V
250 V
5 A
30 A for 0.5 s (NO contact)
5 A continuous
30 A for 0.5 s
-
5 ms
≥ 19 VDC
≤ 10 VDC
≥ 88 VDC
≤ 44 VDC
≥ 176 VDC
≤ 88 VDC
NO/NC (switch se-
1
lectable)
)
1
8 ms
7SD610 Manual