SECTIOn 6 |
tAble 6.6 ProgrAmmAble AnD DefAult PArAmeterS - grouP "other functionS"
Parameter name
"Power SAving"
"enter Point"
"wAKe uP Point"
"remote Switch"
for ON /Off control
through external 12V
signal fed to remote
ON / Off terminals on
the front Panel (15,
fig 2.1)
"relAy function"
(for Status relay)
86 | SAMLEX AMErICA INC.
Operation, Protections and Troubleshooting
Setting range
EVO-
EVO-
2212
3012
1 = Enable 0 = Disable
4 – 50W
5 – 50W
0 = button type: 12V signal is fed
through Push button Type of Switch
Pressing of Push button > 2 sec
will switch the unit ON
When ON, pressing Push button
> 5 sec will turn the unit Off
1 = Switch type: 12V signal is fed
through contacts of Toggle Type of
Switch or relay contact
ON condition (contacts closed)
will turn the unit ON
Off condition (contacts open)
for 2 sec will switch the unit Off
0 = charge / other
Off in "Charging" Mode
ON in other Modes i.e. "Inverting",
"Power Saving" or "Standby"
1 = normal / fault
Off in normal operating conditions
ON in fault Modes
2 = generator 0
ON when batteries drop to "LOW
VOLT ALArM" or lower for period
= "GS DETECT TIME" - Initiates
Generator start
Off after batteries are completely
charged till float Stage - initiates
Generator stop
3 = generator 1
ON when batteries drop to "LOW
VOLT ALArM" or lower for period
= "GS DETECT TIME" - initiates
Generator start
Off when batteries are charged
to "rESET VOLTAGE" for period =
"GEN Off TIME" - initiates Genera-
tor stop
4 = generator 2
ON when batteries drop to "LOW
VOLT ALArM" or lower for period
= "GS DETECT TIME" - initiates
Generator start
Off after period = "GEN ON TIME"
from the time relay switched ON -
initiates Generator stop
EVO-
EVO-
EVO-
2224
4024
2212
6W
7W
cAution! ON/Off Logic also controls the
operation of the ON/Off button on the
front panel (11, fig 2.1). The Default setting
is "button Type".
If the ON/Off Control is changed to external
"remote Switch", it will not be possible to
switch ON/Off the EVO Inverter/Charger
from the front panel ON/Off Push button
because it will work with Switch Type
Logic. It will be ON only as long as the Push
buttom is kept pressed and will switch Off
when released.
Default value
EVO-
EVO-
3012
2224
Enable
8W
6W
10W
7W
0 = button Type
2 = Generator 0
Table continues on next page }
EVO-
4024
8W
10W