SECTIOn 3 |
Insert the terminated end of the wire fully into the terminal slot till it stops. Tighten the screw
firmly. Tightening torque for the screws – 7 to 12 Kgf*cm / 0.5 to 0.9 lbf*ft.
3.7.2 tightening torques
Tightening torques to be applied to the wiring terminals are given in Table below:
battery input
connectors
70 kgf.cm
(5.0 lbf.ft)
3.8 SiZing of wiring AnD breAKerS - Ac inPut SiDe
wArning!
AC breakers for the AC input circuits have NOT been provided internally. These have to be
provided externally by the installer / user based on guidelines given below. Please note that
guidelines given below on wire sizing and over-current protection will be superseded by the
applicable National / Local Electrical Codes.
Attention!
Breakers AC pour les circuits d'entrée AC ont pas été fournis en interne. Ceux-ci doivent être fournies à l'extérieur par
l'installateur / utilisateur sur la base des directives données ci-dessous. Se il vous plaît noter que les directives ci-dessous
sur dimensionnement des câbles et protection contre les surintensités seront remplacées par les nationaux / codes
électriques locaux applicables.
3.8.1 tables for wire and breaker Sizing - Ac input Side
Tables 3.2.1 to 3.2.3 provide details of wire and breaker sizing for the AC input side.
table 3.2.1: for EVO-2212, 2224, 3012 and 4024 for AC Input Current Limit ("GrID
MAX CurrENT" / "GEN MAX CurrENT") set at 30A (Default Setting)
table 3.2.2: for EVO-2212, 2224, 3012 and 4024 for full rated AC input currents.
46 | SAMLEX AMErICA INC.
Installation
Stripped Wire End
fig 3.11 Stripped wire end terminal on Ac wiring
tightening torQueS
external charger input
connectors
35 kgf.cm
(2.5 lbf.ft)
Crimp barrel Portion
Wire End Terminal
Ac input and output
connectors
7 to 12 kgf.cm
(0.5 to 0.9 lbf.ft)