Section 4 - Samlexpower Evolution EVO-2212 Owner's Manual

Inverter/charger pure sine wave
Hide thumbs Also See for Evolution EVO-2212:
Table of Contents

Advertisement

SECTIOn 3 |
i
info for table 3.2.1 (column 8)
AC input breaker size of 40A (Column 8) and corresponding AC input wire size of
AWG #8 (Column 7) for all the 4 models is based on the default AC input current limit
of 30A (Column 7). The AC input current limit in EVO is a programmable parameter
specified as "GrID MAX CurrENT" and "GEN MAX CurrENT" (see Section 4.5 of
Owner's Manual for remote Control EVO-rC at Appendix - A). The 30A default AC
input current has been used to match the standard 30A mains power inlet plug (using
30A cord) on motorhomes / rVs.
for using the full rated AC input current capacities of the 4 models (Column 4), higher
AC input current limits ("GrID MAX CurrENT" / "GEN MAX CurrENT") will have to
be programmed using the optional remote Control Model EVO-rC. AC input breakers
and AC input wiring sizes will also change. In this regard, please refer to Table 3.2.2.
tAble 3.2.2
model no. and
rated
rated output
Ac Pass
Power in in-
through
verter mode
current
(See note
(column 1)
(column 2)
EVO-2212
(2200VA, 18A)
EVO-2224
(2200VA, 18A)
EVO-3012
(3000VA, 25A)
EVO-4024
(4000VA, 33A)
noteS for tAbleS 3.2.1 AnD 3.2.2 - SiZing of griD AnD generAtor inPut
wiring AnD breAKerS
1) Column 2 indicates the rated AC Pass Through Current when in Charger / Pass
Through Mode (value of this current = rated AC Output Current in Inverter Mode).
2) Column 3 indicates the rated AC Side Charging Current in Charger / Pass Through
Mode.
3) Column 4 indicates the total rated AC Input Current which is the sum of the rated
AC Pass Through Current (Column 2) and the rated AC Side Charging Current
(Column 3).
48 | SAMLEX AMErICA INC.
Installation
SiZing of griD AnD generAtor inPut wiring AnD breAKerS for full rAteD
Ac inPut currentS for evo-2212, evo-2224, evo-3012, evo-4024
rated Ac
charging
current
(See note
2)
1)
(column 3)
18 A
15A
18A
19A
25A
20A
33A
29A
total rated
Pro-
Ac input
grammed
current
Ac input
(columns
current
2 +3)
limit
[griD mAX
(See note 3)
current/
gen mAX
current]
(See note 4)
(column 5)
(column 4)
33A
33A
37A
37A
45A
45A
62A
62A
nec Ampac-
conductor
ity = 125% of
Size based
column 5
on nec
Ampacity at
(See note 5)
column 6
(See note 6)
(column 6)
(column 7)
41.25A
AWG #8
46.25A
AWG #8
56.25A
AWG #6
AWG #4 or
77.5A
2X AWG #6
external
breaker
Size
based
on nec
Ampacity at
column 6
(See note 7)
(column 8)
45A
50A
60A
80A