SECtION 4 |
a long period of time, the battery may get completely discharged. Hence, a timer is used
to record the duration of "Battery low voltage!" condition. The EVO Inverter Charger will
be completely shut down (LCD Display / LED / Buzzer will be OFF) when the duration of the
"Battery low voltage!" fault condition as described above is equal to the "LV CUT OFF TIME".
Enter Key
SELECT GROUP
CHARGE CURVE

cHARGe MoDe:

Default setting is 3-Stage "Normal Mode" (Parameter Screen setting shows "0=Normal").
The mode can be changed at any time to 4-stage "Equalization Mode" (Change Screen
setting to "1=Equalize"). After "Equalization Mode" is completed (the charger enters Float
Stage after completing Equalization Stage), the screen automatically resets to Normal (0=
Normal).
Enter Key
SELECT GROUP
CHARGE CURVE
on-Line / oFF-Line UPS MoDeS
on-line UPS (Un-interruptible Power Supply) Mode:
i
inFo
The following programmable parameters have been referred to in the description
below. Links to detailed information on these parameters are given below:
" LOW VOLT ALARM": Please refer to Page 8 of Group 1 of Parameter Setup
Menu Map at Fig 4.1, Table 4.4 and Section 4.4
" GS DETECT TIME": Please refer to Page 16 of Group 1 of Parameter Setup
Menu Map at Fig 4.1, Table 4.4 and Section 4.4
" ONLINE OPTIONS": Please refer to Page 14 of Group 1 of Parameter Setup
Menu Map at Fig 4.1, Table 4.4 and Section 4.4
" CHARGE MODE": Please refer to Page 12 of Group 1 of Parameter Setup Menu
Map at Fig 4.1, Table 4.4 and Section 4.4
" GEN OFF TIME": Please refer to Page 18 of Group 1 of Parameter Setup Menu
Map at Fig 4.1, Table 4.4 and Section 4.4
" RESET VOLTAGE": Please refer to Page 7 of Group 1 of Parameter Setup Menu
Map at Fig 4.1, Table 4.4 and Section 4.4
On-line / Off-Line UPS Modes are programmed through Remote Control EVO-RC by setting
"ONLINE MODE" [1=ON]. The Default Setting is Off-Line Mode [0=OFF].
On-line UPS Mode is suitable for installations where both Grid and Photovoltaic (PV) Solar
Battery Charging System are available. It is also desirable in areas where Grid / Utility
energy rates are very high and use of supplementary battery based photovoltaic
power system is more cost effective. In this mode, un-interruptible AC power is provided
by utilizing batteries and the Inverter Section of EVO as the the PRIMARY DC-AC power
source. The Grid is the secondary / back-up AC power source. Even if qualified Grid AC input
22 | SAMLEX AMERICA INC.
Parameter Setup
Up Key x 10
BULK CURRENT
40 A
Up Key x 11
BULK CURRENT
40 A
LV CUT OFF TIME
1200 sec
CHARGE MODE
0=Normal
APPENDIX A