Samlexpower Evolution EVO-2212 Owner's Manual page 124

Inverter/charger pure sine wave
Hide thumbs Also See for Evolution EVO-2212:
Table of Contents

Advertisement

SECtION 4 |
WAKe UP Point:
If the unit is in "Power Save Mode" and the value of the AC power of the load rises to "WAKE
UP POINT", the unit will quit "Power Save Mode" and will start operating in full voltage
"Inverting Mode".
Up Key x 4
SELECT GROUP
CHARGE CURVE
ReMote SWitcH:
This selection is used when ON/OFF control of EVO Inverter Charger is desired through
external 12 VDC signal fed to Remote ON/OFF terminals on the Front Panel of EVO Inverter
Charger (15, Fig 2.1 in EVO Inverter Charger Owner's Manual) On/Off Logic Diagram is
shown in Fig 4.8 below:
0 = Button Type:
1
12VDC input
st
> 2 sec will switch ON
EVO Inverter Charger
1 = Switch Type:
12VDC input is
available - Power On
Fig 4.8. on/off Logic Diagram for Remote Switch options
!
cAUtion!
On/Off Logic shown in Fig 4.8 also controls the operation of the On/Off Button on the front
panel of EVO Inverter Charger (11, Fig 2.1 in EVO Inverter Charger Owner's Manual). The
Default Setting is "Button Type".
!
Attention!
Logique On / Off montré dans la figure 4,8 contrôle également le fonctionnement du bouton ON/OFF sur le panneau
d'avant de l'onduleur chargeur de l' EVO (11 , figure 2,1 dans le manuel d'EVO onduleur chargeur propriétaire ) . Le
réglage par défaut est « Button Type ».
If the On/Off control is changed to external "Remote Switch", it will not be possible to switch
On/Off the EVO Inverter Charger from the front panel On/Off Push Button because it will
work with Switch Type Logic at Fig 4.8: it will be ON only as long as the Push Button is kept
pressed and will switch off when released.
Up Key x 4
SELECT GROUP
CHARGE CURVE
32 | SAMLEX AMERICA INC.
Parameter Setup
Enter Key
SELECT GROUP
OTHER FUNCTION
12VDC signal is fed through Push Button Type of Switch.
Momentary contact of Push Button > 2 sec will switch EVO Inverter Charger ON
After power ON,
12VDC input < 5 sec
will have no effect
Enter Key
SELECT GROUP
OTHER FUNCTION
POWER SAVING
1 = Enable
No 12VDC input
for 2 sec - Off
POWER SAVING
1 = Enable
APPENDIX A
Up Key x 2
WAKE UP POINT
7W / 10W
After power ON,
12VDC input > 5 sec
will switch OFF
EVO Inverter Charger
Up Key x 3
REMOTE SWITCH
0 = Button

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents