SECtION 4 |
This compensation voltage will affect the Absorbtion Voltage/Equalize Voltage/Floating Voltage/
Batt Over Volt/Restart Voltage/Low Volt Alarm/Batt Low Voltage when the Temperature Sensor
is installed on the battery (see Fig 2.5 in the Owner's Manual for EVO Inverter Charger).
Enter Key
SELECT GROUP
CHARGE CURVE
BAtt oVeR VoLt:
This parameter sets the upper battery voltage threshold at which inverting / charging
operations are switched OFF to protect the unit against damage due to battery overvoltage:
• Ac input is not available and eVo inverter charger is operating in inverting
Mode: When the battery voltage rises to the set upper threshold of "BATT OVER VOLT",
the Inverter Section will be shut down and fault message "Battery over voltage!" will be
displayed on the LCD screen. The Green LED marked "Status" will switch OFF and the
Red LED marked "Fault" will remain ON steady. The buzzer on EVO Inverter Charger will
beep steady. The fault will be cleared automatically when the battery voltage drops to 0.5V
below the set upper threshold of "BATT OVER VOLT"
• A c input is available and eVo inverter charger is operating in charging Mode:
When the battery voltage rises to the set upper threshold of "BATT OVER VOLT", the Transfer
Relay will be de-energized, charging and pass through will be stopped and PWM drive to the
Inverter Section will be switched OFF. Fault message "Battery over voltage!" will be displayed
on the LCD screen. The Green LED marked "Status" will switch OFF and the Red LED marked
"Fault" will remain ON steady. The Buzzer on EVO Inverter Charger will beep steady. The fault
will be cleared automatically when the battery voltage drops to 0.5V below to the set upper
threshold of "BATT OVER VOLT". The unit will start in Inverting Mode, synchronize with the AC
input and then, the Transfer Relay will be energized to transfer to AC input at zero crossing.
The unit will, thus, resume operation in "Charging Mode".
Enter Key
SELECT GROUP
CHARGE CURVE
ReSet VoLtAGe:
The inverter will restart when the battery voltage rises above this set value after "Battery low
voltage!" shutdown occurs. If Relay Function is set for "3 = Generator 1", the relay will turn
OFF (See page 35).
Enter Key
SELECT GROUP
CHARGE CURVE
LoW VoLt ALARM:
When inverting, if battery voltage is under the set value, the Red LED marked "Fault" flashes
once per second. The buzzer in EVO Inverter Charger will beep once per second. If Relay
Function is set for Generator, the relay will turn ON. If in On-Line Mode, it will transfer from
Inverting Mode to Charging Mode.
Enter Key
SELECT GROUP
CHARGE CURVE
20 | SAMLEX AMERICA INC.
Parameter Setup
Up Key x 4
BULK CURRENT
40 A
Up Key x 5
BULK CURRENT
40 A
Up Key x 6
BULK CURRENT
40 A
Up Key x 7
BULK CURRENT
40 A
COMPENSATE
mV/C/C
4
BATT OVER VOLT
16.00 V
RESET VOLTAGE
14.0 V
LOW VOLT ALARM
11.00 V