SECTIOn 1 |
6.
The AC input / output wiring terminals are intended for field connection using Copper
conductors that are to be sized based on 75°C and NOT larger than AWG #1(42.4
mm
). See Tables 1.1(a) and 1.1 (b) and for sizing of conductors for AC INPuT circuits
2
and Table 1.2 for sizing of conductors for AC OuTPuT circuits.
7.
Over current protection (AC breakers) for the AC input / output circuits has NOT been
provided and has to be provided by the installer / user. See guidelines at Tables 1.1(a)
and 1.1 (b) for sizing of breakers for AC INPuT circuits and Table 1.2 for sizing of break-
ers for AC OuTPuT circuits. National and Local Electrical Codes will supersede these
guidelines.
8.
The battery terminals are intended for field connection using Copper conductors that
are sized based on 90°C and are LArGEr than AWG #1(42.4 mm
and 1.3(b) for recommended sizes for installation in free air and conduit respectively.
9.
Over current protection (fuse) for battery and External Charger circuits has NOT been
provided and has to provided by the installer / user. See guidelines at Tables 1.3(a) and
1.3(b) for recommended sizes for installation in free air and conduit respectively. National
and Local Electrical Codes will supersede these guidelines.
10. Tightening torques to be applied to the wiring terminals are given in Table 1.4.
11. This unit has been provided with integral protections against overloads.
12. WArNING! To reduce risk of electric shock and fire:
Installation should be carried out by certified installer and as per Local and National
Electrical Codes.
Do not connect to circuit operating at more than 150 Volts to Ground.
Do not connect to AC Load Center (Circuit breaker Panel) having Multi-wire branch
Circuits connected .
both AC and DC voltage sources are terminated inside this equipment. Each circuit
must be individually disconnected before servicing.
Do not remove cover. No user serviceable part inside. refer servicing to qualified
servicing personnel.
Do not mount in zero clearance compartment.
Do not cover or obstruct ventilation openings.
fuse(s) should be replaced with the same type and rating as of the original installed
fuse(s).
13. WArNING! risk of electric shock. use only those GfCIs that are listed at Table 1.5.
Other types may fail to operate properly when connected to this unit.
14. GrOuNDING: The Grounding symbol shown below is used for identifying only the field
wiring equipment-grounding terminal. however, this symbol is usable with the circle
omitted for identifying various points within the unit that are bonded to Ground.
Grounding Symbol / Défaut à la terre
15. Precautions When Working With batteries.
batteries contain very corrosive diluted Sulphuric Acid as electrolyte. Precautions
should be taken to prevent contact with skin, eyes or clothing. Wear eye protection.
4 | SAMLEX AMErICA INC.
Safety Instructions & general Information
). See Tables 1.3(a)
2