Menus 15 to 17
Parameter
Keypad and
SM-I/O Plus
structure
x.20
Digital I/O read word
RO
Uni
0 to 511
Update rate: 8ms x number of dumb modules
This word is used to determine the status of the digital I/O by reading one parameter. The bits in this word reflect the state of Pr x.03 to Pr x.10.
Bit
Digital I/O
0
T2 (I/O 1)
1
T3 (I/O 2)
2
T4 (I/O 3)
3
T6 (DI 4)
4
T7 (DI 5)
5
T8 (DI 6)
6
T21/T22 (Relay 1)
7
T22/23 (Relay 2)
x.21
T2 digital I/O 1 source/destination
x.22
T3 digital I/O 2 source/destination
x.23
T4 digital I/O 3 source/destination
x.24
T6 digital input 4 destination
x.25
T7 digital input 5 destination
x.26
T8 digital input 6 destination
x.27
Relay 1 source
x.28
Relay 2 source
RW
Uni
DE
Pr 0.00 to Pr 21.51
Update rate: Read on drive reset
x.29
Input polarity select
RW
Bit
DE
OFF (0) or On (1)
Update rate: Background read
This parameter changes the logic polarity for digital inputs, but not digital outputs or relay outputs.
Pr x.29=0 (negative logic)
Inputs
<5V = 1, >15V = 0
Non-relay outputs
1 = >15V (high side drivers only)
Relay outputs
0 = open, 1 = closed
x.31
T2 digital I/O 1 output select
x.32
T3 digital I/O 2 output select
x.33
T4 digital I/O 3 output select
RW
Bit
OFF (0) or On (1)
Update rate: Background read
Programmable digital inputs and output
Destination
Terminal
Input
/ Source
2
I/O 1
Pr x.21
3
I/O 2
Pr x.22
4
I/O 3
Pr x.23
294
Parameter
Parameter
display
x.00
description format
NC
PT
US
Parameter
x.09
x.10
x.03
x.04
x.05
x.06
x.07
x.08
PT
US
Pr 0.00
PT
US
On (1)
Pr x.29=1 (positive logic)
<5V = 0, >15V = 1
1 = >15V (high side drivers only)
0 = open, 1 = closed
US
OFF (0)
State
Invert
Pr x.09
Pr x.11
Pr x.10
Pr x.12
Pr x.03
Pr x.13
www.controltechniques.com
Advanced parameter
Macros
descriptions
Output
select
Pr x.31
Pr x.32
Pr x.33
Serial comms
Electronic
Performance RFC mode
protocol
nameplate
Unidrive SP Advanced User Guide
Issue Number: 10