Emerson unidrive sp User Manual page 324

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Menus 15 to 17
Parameter
Keypad and
SM-I/O 32
structure
x.03
Digital I/O 3 state
x.04
Digital I/O 4 state
x.05
Digital I/O 5 state
x.06
Digital I/O 6 state
x.07
Digital I/O 7 state
x.08
Digital I/O 8 state
x.09
Digital I/O 1 state
x.10
Digital I/O 2 state
RO
Bit
OFF (0) or On (1)
Update rate: 4ms write
Pr x.03 to Pr x.10 show the state of I/O lines DIO1 to DIO8. These bits reflect the I/O state even if fast update mode is being used.
x.11
Digital I/O 1 invert
x.12
Digital I/O 2 invert
x.13
Digital I/O 3 invert
x.14
Digital I/O 4 invert
x.15
Digital I/O 5 invert
x.16
Digital I/O 6 invert
x.17
Digital I/O 7 invert
x.18
Digital I/O 8 invert
RW
Bit
OFF (0) or On (1)
Update rate: Background read
Pr x.11 to Pr x.18 inverts DIO1 to DIO8 respectively for the standard update method. Each bit (DIO1 to DIO8) can be inverted individually.
x.20
Digital I/O read word
RO
Uni
0 to 255
Update rate: 4ms write
This parameter allows the state of DIO1 to DIO8 to be monitored by reading one parameter. It is a read only parameter which shows value of bits 0 to
7 (or DIO1 to DIO8) in decimal from 0 to 255. DIO9 to DIO32 have no affect on this parameter. The bits in this parameter reflect the state of Pr x.03 to
Pr x.10 as follows:
Bit
Digital I/O
Parameter
0
DIO1
Pr x.09
1
DIO2
Pr x.10
2
DIO3
Pr x.03
3
DIO4
Pr x.04
4
DIO5
Pr x.05
5
DIO6
Pr x.06
6
DIO7
Pr x.07
7
DIO8
Pr x.08
324
Parameter
Parameter
display
x.00
description format
NC
PT
OFF (0)
US
OFF (0)
NC
PT
www.controltechniques.com
Advanced parameter
Macros
descriptions
Serial comms
Electronic
Performance RFC mode
protocol
nameplate
Unidrive SP Advanced User Guide