Emerson unidrive sp User Manual page 353

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Parameter
Keypad and
Parameter
structure
display
x.00
x.02
Solutions Module software version
RO
Uni
00.00 to 99.99
Update rate: Write on power-up
This parameter shows the version of software programmed into the Solutions Module. The software sub version is displayed in Pr x.51.
These two parameters display the software version in the form of xx.yy.zz, where:
Pr x.02 = xx.yy
Pr x.51 = zz
x.50
Solutions Module error status
RO
Uni
0 to 255
Update rate: Background write
The error status is provided so that only one option error trip is required for each Solutions Module slot. If an error occurs, the reason for the error is
written to this parameter and the drive may produce an 'SLx.Er' trip (where x is the slot number). A value of zero indicates that the Solutions Module
has not detected an error, a non-zero value indicates that an error has been detected. (See Table 5-39 on page 352 for the meaning of the values in
this parameter for Fieldbus category modules). When the drive is reset, this parameter is cleared.
This Solutions Module includes a temperature monitoring circuit. If the PCB temperature exceeds 90°C, the drive fan is forced to operate at full speed
(for a minimum of 10s). If the temperature falls below 90°C, the fan can operate normally again. If the PCB temperature exceeds 100°C, the drive will
trip on SLx.Er, and the error status is set to 74.
x.51
Solutions Module software sub-version
RO
Uni
0 to 99
Update rate: Write on power-up
The Solutions Module includes a processor with software. The software version is displayed in Pr x.02 and Pr x.51 in the form Pr x.02 = xx.yy and Pr
x.51 = zz.
Where:
xx specifies a change that affects hardware compatibility
yy specifies a change that affects product documentation
zz specifies a change that does not affect the product documentation
When a Solutions Module is installed that does not contain software, both Pr x.02 and Pr x.51 appear as zero.
Unidrive SP Advanced User Guide
Issue Number: 10
Parameter
Advanced parameter
description format
descriptions
NC
PT
NC
PT
NC
PT
www.controltechniques.com
Serial comms
Electronic
Macros
protocol
nameplate
Menus 15 to 17
Performance RFC mode
Fieldbus
353