Upper Current Threshold; Lower Current Threshold; Brake Release Frequency; Brake Apply Frequency - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Parameter
Keypad and
Parameter
structure
display
x.00

Upper current threshold

12.42
Drive modes
Open-loop
Coding
Bit
SP
Range
Open-loop
Default
Open-loop
Update rate
Background read

Lower current threshold

12.43
Drive modes
Open-loop
Coding
Bit
SP
Range
Open-loop
Default
Open-loop
Update rate
Background read
The current magnitude is compared to an upper and lower threshold by a comparator with hysteresis to give torque present and drive output open
detection functions respectively. The upper and lower threshold currents are given as a percentage of motor current defined by Pr 5.07 (or Pr 21.07 if
motor map 2 is selected). The upper threshold should be set to the current level that indicates that there is magnetizing current and sufficient torque
producing current in the motor to deliver the required amount of torque when the brake is released. The output of the comparator remains active after
this level has been reached unless the current subsequently falls below the lower threshold which should be set to the required level to detect the
condition where the motor has been disconnected from the drive. If the lower threshold is set greater or equal to the upper threshold, the upper
threshold applies with a hysteresis band of zero. If Pr 12.42 and Pr 12.43 are both set to zero then the output of the comparator is always one.

Brake release frequency

12.44
Drive modes
Open-loop
Coding
Bit
SP
Range
Open-loop
Default
Open-loop
Update rate
Background read
The frequency comparator can be used to detect when the motor frequency has reached a level where the motor can produce the required amount of
torque to ensure that the motor rotates in the demanded direction when the brake is released. This parameter should be set to a level slightly above
the motor slip frequency that is likely to occur under the highest expected load that is applied to the motor when the brake is released.

Brake apply frequency

12.45
Drive modes
Open-loop
Coding
Bit
SP
Range
Open-loop
Default
Open-loop
Update rate
Background read
The brake apply frequency threshold is used to ensure that the brake is applied before the motor frequency reaches zero and to prevent the motor
rotating (in the reverse direction due to an overhauling load for example) during the brake apply time. If the frequency falls below this threshold, but
the motor is not required to stop (i.e. reversing direction without stopping), provided the Reference on parameter (Pr 1.11) remains at one, the brake
is not applied. This prevents the brake from activating and de-activating as the motor passes through zero speed.
Unidrive SP Advanced User Guide
Issue Number: 10
Parameter
Advanced parameter
description format
descriptions
FI
DE
Txt VM DP ND
0 to 200 %
50
FI
DE
Txt VM DP ND
0 to 200 %
10
FI
DE
Txt VM DP ND
1
0.0 to 20.0 Hz
1.0
FI
DE
Txt VM DP ND
1
0.0 to 20.0 Hz
2.0
www.controltechniques.com
Serial comms
Macros
protocol
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
Electronic
Performance RFC mode
nameplate
PS
1
PS
1
PS
1
PS
1
Menu 12
227