Action On Enable; Low Frequency Voltage Boost; Rated Rpm Auto-Tune - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Parameter
Keypad and
Parameter
structure
display
x.00
5.14

Action on enable

Drive modes
Servo
Bit
SP
Coding
Range
Servo
Default
Servo
Update rate
Background read
This parameter defines the action taken on enable as follows:
0: nonE
No action.
1: Ph Enl
A minimal movement phasing test is performed each time the drive is enabled (i.e. changes from the inhibit state to either the stop or run state). The
test can be used to determine the phasing angle for an absolute or non-absolute type encoder. If the test is completed successfully the drive changes
to the stop or run state as appropriate. The phasing angle parameter is updated to the correct value, but it is not saved to EEPROM or the SMART
card.
2: Ph Init
A minimal movement phasing test is performed the first time the drive is enabled after power-up. The test will only be performed again on enable if the
position feedback device(s) have been re-initialized. Re-initialization occurs for example after a trip specifically related to an encoder where position
information may have been lost. Initialization occurs when parameter 03.48 changes from zero to one. The phasing angle parameter is updated to the
correct value, but it is not saved to EEPROM or the SMART card.
5.15

Low frequency voltage boost

Drive modes
Open-loop, Closed-loop vector
Bit
SP
Coding
Range
Open-loop, Closed-loop vector
Default
Open-loop, Closed-loop vector
Update rate
Background read
The voltage boost is used in fixed boost mode and square law mode for Open-loop mode, and during the rotating auto-tune test in Closed-loop vector
mode.In open-loop mode the default is dependant on the frame size as given in the table below.
Drive sizes
SP0xxx,SP1xxx, SP2xxx, SP3xxx
SP4xxx, SP5xxx
SP6xxx to SP9xxx, SPMxxxxx
5.16

Rated rpm auto-tune

Drive modes
Closed-loop vector
Bit
SP
Coding
Range
Closed-loop vector
Default
Closed-loop vector
Update rate
Background read
The motor rated full load rpm parameter (Pr 5.08) in conjunction with the motor rated frequency parameter (Pr 5.06) defines the full load slip of the
motor. The slip is used in the motor model for closed-loop vector control. The full load slip of the motor varies with rotor resistance which can vary
significantly with motor temperature. When this parameter is set to 1 or 2 the drive can automatically sense if the value of slip defined by Pr 5.06 and
Pr 5.08 has been set incorrectly or has varied with motor temperature. If the value is incorrect Pr 5.08 is automatically adjusted. Pr 5.08 is not saved
at power-down, and so when the drive is powered-down and up again it will return to the last value saved by the user. If the new value is required at
the next power-up it must be saved by the user. Automatic optimization is only enabled when the frequency is above rated frequency/8, and when the
load on the motor load rises above
correct values of stator resistance (Pr 5.17), transient inductance (Pr 5.24), stator inductance (Pr 5.25) and saturation breakpoints (Pr 5.29 and Pr
5.30) should be stored in the relevant parameters. Rated rpm auto-tune is not available if the drive is not using external position/speed feedback
(RFC mode).
The gain of the optimizer, and hence the speed with which it converges, can be set at a normal low level when Pr 5.16 is set to 1. If this parameter is
set to 2 the gain is increased by a factor of 16 to give faster convergence.
The rated rpm optimizer is automatically disabled when closed-loop vector RFC mode is selected (Pr 3.24=1 or 3).
Unidrive SP Advanced User Guide
Issue Number: 10
Parameter
Advanced parameter
description format
descriptions
FI
DE
TE
VM DP
ND
1
0 to 2
0
FI
DE
Txt VM DP
ND
1
0.0 to 25.0 % of motor rated voltage
See below
Default
3.0%
2.0%
1.0%
FI
DE
Txt VM DP
ND
0 to 2
0
5
/
rated load. Optimization is disabled again if the load falls below half rated load. For best optimization results the
8
www.controltechniques.com
Serial comms
Macros
protocol
RA
NC
NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC
NV
PT
US RW BU
1
1
Electronic
Performance RFC mode
nameplate
PS
1
PS
1
PS
Menu 5
123