Parameter X.00 Reset; Saving Parameters In Drive Eeprom - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Parameter
Keypad and
structure
display
3
Parameter x.00
Parameter x.00 is available in all menus and has the following functions.
Value
Save parameters when under voltage is not active
1000
(Pr 10.16 = 0) and 48V supply is not active (Pr 6.44 = 0).
1001
Save parameters under all conditions
1070
Reset all Solutions Modules
1233
Load standard defaults
1244
Load US defaults
1253
Change drive mode with standard defaults
1254
Change drive mode with US defaults
Change drive mode with standard defaults (excluding
1255
menus 15 to 20)
Change drive mode with US defaults (excluding menus
1256
15 to 20)
Transfer drive parameter to a card and create a bootable
difference from default SMART card block with data
2001
block number 1 and clear Pr 11.42. If data block 1 exists
it is over written.
Transfer drive EEPROM data to a SMARTCARD block
3yyy
number yyy
Transfer drive data as difference from defaults to
4yyy
SMARTCARD block number yyy
Transfer drive ladder program to SMARTCARD block
5yyy
number yyy
6yyy
Transfer SMARTCARD data block yyy to the drive
7yyy
Erase SMARTCARD data block yyy
8yyy
Compare drive parameters with block yyy
9555
Clear SMART card warning suppression flag
9666
Set SMART card warning suppression flag
9777
Clear SMARTCARD read-only flag
9888
Set SMARTCARD read-only flag
9999
Erase SMARTCARD
Transfer electronic nameplate parameters to/from drive
110zy
from/to encoder
*12000
Display non-default values only
*12001
Display destination parameters only
*These functions do not require a drive reset to become active. All other
functions require a drive reset.
3.1

Parameter x.00 reset

When an action is started by setting Pr x.00 to one of the above values
and initiating a drive reset this parameter is cleared when the action is
completed successfully. If the action is not started, e.g. because the
drive is enabled and an attempt is made to load defaults, etc., Pr x.00 is
not cleared and no trip is produced. If the action is started and then fails
for some reason a trip is always produced and Pr x.00 is not cleared. It
should be noted that parameter saves etc. can also be initiated with the
copying parameter (Pr 11.42). If actions that can be initiated by either
parameter are started and then completed successfully Pr x.00 is
cleared and Pr 11.42 is cleared if it has a value of less than 3.
It should be noted that there could be some conflict between the actions
of Pr x.00 and Pr 11.42 (Parameter copying) when the drive is reset. If
Pr 11.42 has a value of 1 or 2 and a valid action is required from the
value of Pr x.00 then only the action required by Pr x.00 is performed.
Pr x.00 and Pr 11.42 are then reset to zero. If Pr 11.42 has a value of 3
or 4 it will operate correctly causing parameters to be save to a smart
card each time a parameter save is performed.
16
Parameter
Parameter
Advanced parameter
x.00
description format
Action
www.controltechniques.com
Serial comms
Macros
descriptions
3.2

Saving parameters in drive EEPROM

Drive parameters are saved to drive EEPROM by setting Pr x.00 to 1000
or 1001 and initiating a drive reset. In addition to user save parameters,
power down save parameters are also saved by these actions and by
changing drive mode, but not by any other actions that result in
parameters being saved to drive EEPROM (i.e. loading defaults). Power
down save parameters are not saved at power down unless the drive is
supplied from a normal mains supply, and so this gives the user the
option of saving these parameters when required. When the parameter
save is complete Pr x.00 is reset to zero by the drive. Care should be
taken when saving parameters because this action can take between
400ms and several seconds depending on how many changes are
stored in the EEPROM. If the drive is powered down during a parameter
save it is possible that data may be lost. When the drive is operating
from a normal mains supply then it will stay active for a short time after
the power is removed, however, if the drive is being powered from a 24V
control supply, or it is being operated from a low voltage battery supply,
the drive will power down very quickly after the supply is removed. The
drive provides two features to reduce the risk of data loss when the drive
is powered down.
1. If Pr x.00 is set to 1000 a parameter save is only initiated on drive
reset if the drive is supplied from a normal mains supply (Pr 10.16 =
0 and Pr 6.44 = 0). 1001 must be used to initiate a save if the drive is
not supplied from a normal mains supply.
2. Two banks of arrays are provided in EEPROM to store the data.
When a parameter save is initiated the data is stored in a new bank
and only when the data store is complete does the new bank
become active. If the power is removed before the parameter save is
complete a SAVE.Er trip (user save parameter save error) or
PSAVE.Er trip (power down save parameter save error) will be
produced when the drive is powered up again indicating that the
drive has reverted to the data that was saved prior to the last
parameter save.
The second feature will significantly reduce the possibility of completely
invalidating all saved data, which would result in an EEF trip on the next
power-up. However the following points should be noted:
1. If the power is removed during a parameter save the current data
that is being saved to the EEPROM that is different from the last
data saved in the EEPROM will be lost and SAVE.Er or PSAVE.Er
trip will occur on power-up.
2. This feature does not apply when user save parameters are saved
automatically by adjusting the values in menu 0 with an LED keypad.
However, the time taken to save parameters in this way is very short,
and is unlikely to cause data loss if the power is removed after the
parameter has been changed. It should be noted that any parameter
changes made in this way are included in the currently active bank in
the EEPROM, so that if the power is removed during a subsequent
save initiated via Pr x.00 that results in an SAVE.Er trip, the changes
made via menu 0 will be retained and not lost.
3. User save parameters are saved to drive EEPROM after a transfer
of data from an electronic nameplate in an encoder.
4. User save parameters are saved to drive EEPROM after a transfer
of data from a SMART card.
5. This feature is not provided for data saved to a SMART card, and so
it is possible to corrupt the data files on a SMART card if the power is
removed when data is being transferred to the card.
6. User save parameters are saved to drive EEPROM after defaults
are loaded.
Electronic
Performance
protocol
nameplate
Unidrive SP Advanced User Guide
RFC mode
Issue Number: 10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents