Emerson unidrive sp User Manual page 315

Universal variable speed ac drive for induction and servo motors
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Parameter
Keypad and
Parameter
structure
display
x.00
x.21
T1 digital input 1 destination
x.22
T2 digital input 2 destination
x.23
T4 digital input 3 destination
x.24
T5 digital input 4 destination
x.25
T7 digital input 5 destination
x.26
T8 digital input 6 destination
RW
Uni
DE
Pr 0.00 to Pr 21.51
Update rate: Read on drive reset
x.27
Relay 1 source
x.28
Relay 2 source
RW
Uni
Pr 0.00 to Pr 21.51
Update rate: Read on drive reset
x.50
Solutions Module error status
RO
Uni
0 to 255
Update rate: Background read
The error status is provided so that only one option error trip is required for each Solutions Module slot. If an error occurs, the reason for the error is
written to this parameter and the drive may produce a SLx.Er trip, where x is the slot number. A value of zero indicates that the Solutions Module has
not detected an error, a non-zero value indicates that an error has been detected. (See Table 5-25 on page 312 for the meaning of the values in this
parameter). When the drive is reset, this parameter is cleared for the relevant Solutions Module.
This Solutions Module includes a temperature monitoring circuit. If the PCB temperature exceeds 90°C, the drive fan is forced to operate at full speed
for a minimum of 10s on Unidrive SP. If the temperature falls below 90°C, the fan can operate normally again. If the PCB temperature exceeds 100°C,
the drive is tripped and the error status is set to 74.
x.51
Solutions Module software sub-version
RO
Uni
0 to 99
Update rate: Write on power-up
The Solutions Module includes a processor with software. The software version is displayed in Pr x.02 and Pr x.51 in the form Pr x.02 = xx.yy and
Pr x.51 = zz.
Where:
xx specifies a change that affects hardware compatibility
yy specifies a change that affects product documentation
zz specifies a change that does not affect the product documentation
When a Solutions Module is installed that does not contain software, both Pr x.02 and Pr x.51 appear as zero.
Unidrive SP Advanced User Guide
Issue Number: 10
Parameter
Advanced parameter
description format
descriptions
US
Pr 0.00
US
Pr 0.00
NC
PT
NC
PT
www.controltechniques.com
Serial comms
Electronic
Macros
protocol
nameplate
Menus 15 to 17
Performance RFC mode
SM-I/O 120V
315

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents