Parameter
Keypad and
Parameter
structure
display
x.00
x.20
Digital I/O read word
RO
Uni
0 to 255
Update rate: 500μs write
This word is used to determine the status of the digital I/O by reading one parameter. The bits in this word reflect the state of Pr x.03 to Pr x.10.
Bit
Digital I/O
0
T3 (Digital I/O 1)
1
T4 (Digital I/O 2)
2
T5 (Digital I/O 3)
3
T6 (Digital I/O 4)
4
T7 (Digital input 5)
5
T2 (PELV user power supply state)
6
T14 / T15 (Digital output 7 relay)
7
T16 / T17 (Digital output 8 relay)
x.21
T3 digital I/O 1 source/destination
x.22
T4 digital I/O 2 source/destination
x.23
T5 digital I/O 3 source/destination
x.24
T6 digital I/O 4 source/destination
x.25

T7 digital input 5 destination

RW
Uni
DE
Pr 0.00 to Pr 21.51
Update rate: Read on drive reset
Source parameters define the parameter to be represented by the digital output terminal.
Destination parameters define the parameter each of the programmable inputs is to control.
x.27
Relay 1 source
x.28
Relay 2 source
RW
Uni
Pr 0.00 to Pr 21.51
Update rate: Read on drive reset
Source parameters define the parameter to be represented by the digital output terminal.
x.29
T6 digital I/O 4 output select
RW
Bit
OFF (0) or On (1)
Update rate: Background read
This parameter selects the function of terminal T6 as follows:
OFF (0) = digital input
On (1)
= digital output
x.31
T3 digital I/O 1 output select
x.32
T4 digital I/O 2 output select
x.33
T5 digital I/O 3 output select
RW
Bit
OFF (0) or On (1)
Update rate: Background read
These parameters select the function of terminals T3 to T5 as follows:
OFF (0) = digital input
On (1) = digital output
Unidrive SP Advanced User Guide
Issue Number: 10
Parameter
Advanced parameter
description format
descriptions
NC
PT
US
Parameter
Pr x.09
Pr x.10
Pr x.03
Pr x.04
Pr x.05
Pr x.06
Pr x.07
Pr x.08
US
Pr 0.00
US
Pr 0.00
US
On (1)
US
OFF (0)
www.controltechniques.com
Serial comms
Electronic
Macros
protocol
nameplate
Bit Update Rate
Input/Output
500μs / 4ms
500μs / 4ms
500μs / 4ms
500μs / 4ms
500μs / -
500μs / -
- / 4ms
- / 4ms
Menus 15 to 17
Performance RFC mode
SM-I/O PELV