Emerson EC3-D72 Operating	 Instruction

Emerson EC3-D72 Operating Instruction

Ec3-d7x digital superheat controller with tcp/ip communication capability
Hide thumbs Also See for EC3-D72:

Advertisement

Available languages

Available languages

Quick Links

G e n e r a l i n f o r ma t i o n :
EC3-D72 is the superheat controller with TCP/IP connection for stepper motor
driven Electrical Control Valves EX4-6 from EMERSON and is optimized to operate
with the Copeland Digital Scroll series utilizing a 0-10V input from a third-party
controller. The controller synchronizes the PWM digital compressor solenoid valve
with the superheat controlled by the electrical control valve; EX series.
The EC3-D73 has the same functionality but can only be set-up via the ECD-002
display. It has no external communication functionality.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure to comply can result in device
failure, system damage or personal injury.
• According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
• Do not exceed the specified maximum ratings for pressure, temperature,
voltage and current.
• Before installation or service disconnect all voltages from system and device.
• Do not operate system before all cable connections are completed.
• Entire electrical connections have to comply with local regulations.
Note: The EC3-D7x series contains
lead-acid battery.
The battery must NOT be disposed of with other commercial waste.
Instead, it is the user's responsibility to pass it to a designated collection point for the
safe recycling of batteries (harmonized directive 2012/19/EU). For further
information contact your local environmental recycling center.
M o u n t i n g p o s i t i o n :
The EC3-D7x is designed to be mounted onto a standard DIN rail. Mounting
position: on vertical walls, with stepper motor connector on top side only.
M o u n t i n g o f E C D - 0 0 2 :
• ECD-002 can be installed at any time also during operation.
• ECD-002 can be mounted in panels with
71x29 mm cutout.
• Push controller into panel cut-out.(1)
• Make sure that mounting lugs are flush with
outside of controller housing
• Insert Allen key into front panel holes and turn
clockwise. Mounting lugs will turn and gradually
move towards panel (2)
• Turn Allen key until mounting lug barely touches
panel. Then move other mounting lug to the same
position (3)
• Tighten both sides very carefully until keypad is
secured. Do not over tighten as mounting lugs
will break easily.
!
E l e c t r i c a l I n s t a l l a t i o n :
• Refer to the electrical wiring diagram for electrical connections.
• Do not apply voltage to the controller before completion of wiring.
• Ground the metal housing with a 6.3 mm spade connector.
• Keep controller and sensor wiring well separated from mains wiring. Minimum
recommended distance 30 mm.
• Use a class II category transformer for 24 VAC power supply. Do not ground the
24 VAC lines. We recommend using individual transformers for EC3 controller(s)
rd
and for 3
party controllers to avoid possible interference or grounding problems
in the power supply. Connecting any EC3 inputs to mains voltage will permanently
damage the EC3.
• The use of the relay is essential to protect the system in case of power failure if the
communications interface or the ECD-002 are not utilized.
• If the output relay is not utilized, the user must ensure appropriate safety pre-
cautions are in place to protect the system against damage caused by a power
failure.
• In order to provide system protection in the event of power loss, it is recommended
to change the battery annually.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Operating instruction
EC3-D7x Digital Superheat Controller
EC3-D72 with TCP/IP communication capability
a VRLA battery = valve regulated rechargeable
www.emersonclimate.eu
Digital input status is dependent to operation of compressor/0-10V input
System
Digital Inputs
Operating
condition
C1 &
"Cooling demand" open (0 V)
C2 in stop mode
"Comp 2 Running" open (0 V)
C1 in run &
"Cooling demand" closed (24 V)
C2 in stop mode
"Comp 2 Running" open (0 V)
C1 &
"Cooling demand" closed (24 V)
C2 in run mode
"Comp 2 Running" closed (24 V)
C1 in stop &
"Cooling demand" open (0 V)
C2 starts run
"Comp 2 Running" closed (24 V)
mode
Note 1: C1 = Compressor 1, C2 = Compressor 2
Note 2: Digital comp. should always be regarded as base load compressor 1.
W i r i n g :
A:
White wire
B:
Black wire
C:
Blue wire
D:
Brown wire
E:
M12 Plug cable assembly EXV-Mxx for connection to EX4-6
F:
24 V Triac output to PWM Digital Scroll valve
G:
Remote control panel, system controller.
H:
Alarm relay, dry contact. Relay coil is not energized at alarm or power off.
I:
Digital input "Cooling demand" (0 V/open = Stop; 24 V/closed = Start)
J:
Transformer Class II, 24 VAC secondary / 25 VA
K:
Third party controller (can use the analog output signal from EC3)
L:
Pump down relay, dry contact. Relay is energized during normal operation
M:
Digital input 2: "Comp 2 running"
(0 V/ open = Comp 2 stop; 24 V /closed = Comp. 2 running)
N:
Discharge Temp. Sensor Copeland® NTC
O:
0-10 V Digital Scroll capacity demand signal from system controller
P:
ECN-N60 Temperature sensor
Date: 18.07.2017
0-10V input from third party
controller
EXV remains closed irrespective
of voltage input value
EXV active
Input = 0V: dig. valve capacity =
10% default capacity.
If dig. comp. is in by-pass,
EXV will:
- close if capacity is <70%
- be inhibited if capacity is
>70%
EXV active
EXV always modulates even when
the dig. compr. is in by-pass mode.
EXV remains closed irrespective
of voltage input value
EC3-D7x_OI_ML_R06_865019.docx

Advertisement

loading

Summary of Contents for Emerson EC3-D72

  • Page 1 G e n e r a l i n f o r ma t i o n : Digital input status is dependent to operation of compressor/0-10V input EC3-D72 is the superheat controller with TCP/IP connection for stepper motor System...
  • Page 2 P r e p a r a t i o n f o r S t a r t - u p : (must be checked and modified if necessary) • Vacuum the entire refrigeration system. Factory Field • Note: EMERSON Electrical Control Valves EX4-6 are delivered at half open Code Parameter description and choices Min Max setting setting position.
  • Page 3 • Open the Internet browser program on the computer and, if EC3-D72 is connected Show decimal point; 0=yes, 1 = no directly to PC with a crossover cable enter the default TCP/IP address of the A6 Maximum discharge temperature;...
  • Page 4 Operating instruction EC3-D7x Digital Superheat Controller EC3-D72 with TCP/IP communication capability E r r o r / A l a r m h a n d l i n g : Requires manual Alarm Related Alarm Description Valve What to do?
  • Page 5 Operating instruction EC3-D7x Digital Superheat Controller EC3-D72 with TCP/IP communication capability T e c h n i c a l d a t a Power supply 24 VAC ±10%; 50/60 Hz; 1 A Power consumption 25 VA max. including EX4-6...
  • Page 6 Expansionsventil. EC3-D73 besitzt die gleiche Steuerfunktion V1 & V2 “Cooling demand” offen (0 V) EXV bleibt geschlossen, unabhängig wie EC3-D72 allerdings ohne TCP/IP Schnittstelle; zur Kommissionierung muss eine ausgeschaltet “Comp 2 Running” offen (0 V) vom Eingangssignal.
  • Page 7 V o r b e r e i t u n g e n f ü r I n b e t r i e b n a h m e : (im Regler hinterlegte Reihenfolge) • Den gesamten Kältekreislauf vakuumieren. • Hinweis: Elektrische Regelventile von EMERSON EX4-6 werden halbgeöffnet Code Beschreibung und Wahlmöglichkeiten Min Max Werk Kunde ausgeliefert.
  • Page 8 Beschädigung des Verdichters oder anderer Systemkomponenten. Alle anderen b1 Batterie-Fehlermanagement bei defekter Parameter können jederzeit verändert werden. Batterie: • Der EC3-D72 kann mit seiner TCP/IP Ethernet-Schnittstelle direkt an den Möglichkeit zur Ethernetanschluss eines PCs oder an ein lokales Netzwerk angeschlossen werden. Wert...
  • Page 9 Betriebsanleitung EC3-D7x Digital Scroll Überhitzungsregler EC3-D72 mit TCP/IP Schnittstelle A l a r ma n z e i g e n u n d F e h l e r b e h e b u n g : Manuelle Rückstellung...
  • Page 10 Betriebsanleitung EC3-D7x Digital Scroll Überhitzungsregler EC3-D72 mit TCP/IP Schnittstelle T e c h n i s c h e D a t e n : Versorgungsspannung 24 VAC ±10%; 50/60 Hz; 1 A Leistungsaufnahme 25 VA max, inklusive EX4-6 Steckbare Schraubklemmen für Adern mit max.