Daily And Periodic Inspection Items - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

Chapter 8 - Troubleshooting & Maintenance

8.6 Daily and Periodic Inspection Items

Is there any dust?
Ambient
Is the ambient temperature and humidity
Environ-
adequate?
ment
All
Equipment
Is there any abnormal oscillation or noise?
Input
Is the input voltage of the main circuit
Voltage
normal?
Megger check (between the main circuit and
the ground)
Are any fixed parts removed?
All
Are there any traces of overheating at each
component' s cleaning?
Is the conductor rusty?
Conductor/
Is the wire coating damaged?
Wire
Terminal
Is there any damage?
IGBT
Check the resistance between each of the
Module
terminals.
/Diode
Module
Is there any liquid coming out?
Is the safety pin out, and is there any
Smoothing
swelling?
Capacitor
Measure the capacitance.
Is there any chattering noise during
operation?
Relay
Is there any damage to the contact
Is there any damage to the resistor
insulation?
Resistor
Is the wiring in the resistor damaged (open)?
Is there any unbalance between each
phases of the output voltage?
Nothing must be wrong with display circuit
Operation
Check
after executing the sequence protective
operation.
Is there any abnormal oscillation or noise?
Is the connection area loose?
Cooling
Fan
Is the displayed value correct?
Meter
Are there any abnormal vibrations or noise?
All
Is there any unusual odor?
Insulation
Megger check (between the output terminals
Resistor
and the ground terminal)
Note: Values in ( ) is for the 400V class inverters.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Period
Inspection
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Ο
Inspection Method
Refer to the precautions .
Use sight and hearing.
Measure the voltage between the
terminals R, S, T.
Undo the inverter connections short
the terminals R, S, T, U, V, W and
measure between these parts and the
Ο
ground.
Tighten the screws.
Visual check.
Visual check
Visual check
Undo the inverter connection and
Ο
measure the resistance between R, S,
T ⇔ P, N and U, V, W ⇔ P, N with a
tester.
Visual check
Measure with a capacitance-
measuring device.
Auditory check
Visual check
Visual check
Disconnect one of the connections
and measure with a tester.
Measure the voltage between the
output terminals U, V and W.
Short and open the inverter protective
circuit output.
Turn OFF the power and turn the fan
by hand.
Tighten the connections.
Check the meter reading at the
exterior of the panel.
Auditory , sensory, visual check.
Check for overheat and damage.
Undo the U, V and W connections and
Ο
tie the motor wiring.
188
Measuring
Criterion
Instrument
Temperature:
Thermometer
-10~+40 no
,
freezing.
Hygrometer,
Humidity: Under
Recorder
50% no dew
No abnormality
Digital Multi-
Meter/Tester
Over 5MΩ
DC 500V
class Megger
No fault
No fault
No fault
(Refer ' How to
Digital Multi-
Check Power
Meter/Analog
Components" )
Tester
No fault
Capacitance
Over 85% of the
Measuring
rated capacity
Device
No fault
No fault
Digital Multi-
Error must be
Meter/Analog
within ±10% the
Tester
displayed
resistance.
The voltage
Digital Multi-
balance between
Meter/Rectifyi
the phases for
ng Voltmeter
200V (800V) class
is under 4V (8V).
The fault circuit
operates according
to the sequence.
Must rotate
smoothly.
No fault
Check the
Voltmeter/
specified and
Ammeter etc.
management
values .
No fault
Over 5MΩ
500V class
Megger