Code
Description
Torque Boost in Forward
FU1-27
Direction
Torque Boost in Reverse
FU1-28
Direction
FU1-29 Volts/Hz Pattern
FU1-30
16
User V/F – Frequency 1
FU1-31 User V/F – Voltage 1
FU1-32 User V/F – Frequency 2
FU1-33 User V/F – Voltage 2
FU1-34 User V/F – Frequency 3
FU1-35 User V/F – Voltage 3
FU1-36 User V/F – Frequency 4
FU1-37 User V/F – Voltage 4
Output Voltage
FU1-38
Adjustment
FU1-39 Energy Save Level
Electronic Thermal
FU1-50
Selection
Electronic Thermal Level
FU1-51
17
for 1 Minute
Electronic Thermal Level
FU1-52
for Continuous
Electronic Thermal
FU1-53
Characteristic Selection
(Motor Type)
FU1-54 Overload Warning Level
Overload Warning Hold
FU1-55
Time
FU1-56 Overload Trip Selection
FU1-57 Overload Trip Level
FU1-58 Overload Trip Delay Time
Stall Prevention Mode
FU1-59
Selection
FU1-60 Stall Prevention Level
FU1-99 Return Code
16
Code FU1-30 through FU1-37 appears only when FU1-29 is set to ' User V/F' .
17
Code FU1-51 through FU1-53 appears only when FU1-50 is set to ' Yes' .
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Keypad Display
LCD
7-Segment
Fwd boost
27
Rev boost
28
V/F pattern
29
User freq 1
30
User volt 1
31
User freq 2
32
User volt 2
33
User freq 3
34
User volt 3
35
User freq 4
36
User volt 4
37
Volt control
38
Energy save
39
ETH select
50
ETH 1 min
51
ETH cont
52
Motor type
53
OL level
54
OL time
55
OLT select
56
OLT level
57
OLT time
58
Stall prev.
59
Stall level
60
Not displayed
99
59
Chapter 5 - Parameter List
Setting Range
LCD
7-Segment
0 to 15 [%]
0 to 15 [%]
Linear
0
Square
1
User V/F
2
0 to FU1-20
0 to 100 [%]
0 to FU1-20
0 to 100 [%]
0 to FU1-20
0 to 100 [%]
0 to FU1-20
0 to 100 [%]
40 to 110 [%]
0 to 30 [%]
No
0
Yes
1
FU1-52 to 200 [%]
50 to FU1-51 (Maximum 150%)
Self-cool
0
Forced-cool
1
30 to 150 [%]
0 to 30 [sec]
No
0
Yes
1
30 to 200 [%]
0 to 60 [sec]
000 to 111
(Bit Set)
30 to 250 [%]
Not available
1
Adj.
Factory
During
Units
Page
Default
Run
0.1
2.0 [%]
No
0.1
2.0 [%]
No
-
Linear
No
93
0.01
15.00 [Hz]
No
1
25 [%]
No
0.01
30.00 [Hz]
No
1
50 [%]
No
94
0.01
45.00 [Hz]
No
1
75 [%]
No
0.01
60.00 [Hz]
No
1
100 [%]
No
0.1
100.0 [%]
No
94
1
0 [%]
Yes
94
-
No
Yes
1
180 [%]
Yes
95
1
120 [%]
Yes
-
Self-cool
Yes
1
150 [%]
Yes
96
0.1
10.0 [sec]
Yes
-
Yes
Yes
96
1
180 [%]
Yes
1
60.0 [sec]
Yes
bit
000
No
97
1
180 [%]
No
-
1
-
98