LG SV-iS5 Instruction Manual page 137

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

[Stall]
AXA-AXC is CLOSED when the inverter is on the stall
prevention mode.
Output Current
FU1-60
[Stall Level]
FU1-60
[Stall Level]
Output Frequency
AXA-AXC
[AXA-AXC configured as ' Stall' ]
Related Functions:
FU1-59 [Stall Prevention Mode]
FU1-60 [Stall Prevention Level]
[OV]
AXA-AXC is CLOSED when the DC link voltage is above
the Over-voltage level.
DC Link Voltage
AXA-AXC
ON
[AXA-AXC configured as ' OV' ]
[LV]
AXA-AXC is CLOSED when the DC link voltage is below
the Low-voltage level.
DC Link Voltage
AXA-AXC
[AXA-AXC configured as ' LV' ]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Time
Time
CLOSED
Time
OV Level (380V DC or 760V DC)
Time
Time
LV Level (200V DC or 400V DC)
Time
ON
Time
Chapter 6 - Parameter Description [I/O]
[OH]
AXA-AXC is CLOSED when the heat sink of the inverter
is above the reference level.
[Lost Command]
AXA-AXC is CLOSED when frequency reference is lost.
Related Functions:
I/O-11 [Criteria for Analog Signal Loss]
I/O-48 [Operating Method at Signal Loss]
I/O-49 [Waiting Time for Time Out]
[Run]
AXA-AXC is CLOSED when the inverter is running.
[Stop]
AXA-AXC is CLOSED when the inverter is stopped.
[INV line, COMM line]
This function is used in conjunction with ' Exchange'
function of multi-function input for commercial line
exchange. To use both signal of ' INV line' and 'COMM
line' , the optional Sub-A or Sub-C board must be
installed.
Output Frequency
FX-CM
' Exchange' -CM
AXA-AXC
' COMM line'
Q1-EXTG
ON
' INV line'
Inverter
Drive
[AXA-AXC configured as ' COMM line' and ' Q1' as INV line' ]
Related Functions:
I/O-12 ~ I/O-14 [Multi- function input]
- [Exchange]
131
Speed Search
ON
ON
ON
ON
t1
t2
Commercial
Inverter
Line Drive
Drive
t1, t2: 50msec (interlock time)
Time
Time
Time
Time
Time