LG SV-iS5 Instruction Manual page 135

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

Output V
I/O-41*10 V
10 V
FM-5G
0 %
I/O-44: Multi-function Auxiliary Contact Output
define (AXA-AXC)
I/O?
Aux mode
44
Run
Factory Default:
Run
The auxiliary contact works (Close) when the defined
condition has occurred.
Setting Range
LCD
7-Seg
0
FDT-1
1
FDT-2
2
FDT-3
FDT-4
3
FDT-5
4
5
OL
6
IOL
7
Stall
8
OV
9
LV
10
OH
11
Lost Command
12
Run
13
Stop
14
Steady
15
INV line
16
COMM line
17
Ssearch
18
Step pulse
19
Seq pulse
20
Ready
21
Trv. ACC
22
Trv. DEC
23
MMC
24
Zspd Dect
25
Torq Dect
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
I/O-40
100
44
12
12
Description
Output frequency arrival detection
Specific frequency level detection
Frequency detection with pulse
Frequency detection with contact
closure
Frequency detection with contact
closure (inverted FDT-4)
Overload detection
Inverter overload detection
Stall prevention mode detection
Over voltage detection
Low voltage detection
Overheat detection
Lost command detection
Inverter running detection
Inverter stop detection
Steady speed detection
Exchange signal outputs
Speed search mode detection
Step detection in Auto mode
Sequence detection in Auto mode
Inverter ready detection
Traverse acceleration frequency
Traverse deceleration frequency
Used for MMC operation
0 rpm Detection in Vector control
Torque Detection
Chapter 6 - Parameter Description [I/O]
[FDT-1]
When the output frequency reaches the reference
frequency (target frequency), AXA-AXC terminal is
CLOSED.
Output Frequency
AXA-AXC
[AXA-AXC configured as ' FDT-1' ]
[FDT-2]
AXA-AXC is CLOSED when the reference frequency is
in I/O-43 [FDT Bandwidth] centered on I/O-42 [FDT
Frequency], and the output frequency reaches I/O-43
centered on I/O-42.
Output Frequency
I/O-42
AXA-AXC
CLOSED
[AXA-AXC configured as ' FDT-2' ]
[FDT-3]
AXA-AXC is CLOSED when the output frequency
reaches the band centered on the FDT frequency. The
output is OPENED when the output frequency goes
outside the FDT bandwidth centered on the FDT
frequency.
129
Reference Frequency
I/O-43 / 2
CLOSED
Reference Frequency
I/O-43 / 2
Time
Time
Time
Time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents