Note: When the reference frequency is set inside the jump
frequency, the output frequency goes to the frequency
marked by "
" symbol.
n
Note: If one frequency jump range is required, set all
ranges to the same range.
FU2-17: Start Curve for S-Curve Accel/Decel
Pattern
FU2-18: End Curve for S-Curve Accel/Decel
Pattern
FU2? Start Curve
17
40 %
Factory Default:
40%
FU2? End Curve
18
40 %
Factory Default :
40%
This parameter is used to adjust the Accel and Decel
pattern when ' S-Curve' is selected in FU1-05 and FU1-
06 respectively. To use this function, the Reference
Frequency for Accel and Decel set in FU2-70 should be
set to ' Delta freq' .
Output Frequency
FU2-18
FU2-17
Linear
[S-Curve Adjustment]
Actual Accel Time = DRV-01 + (DRV-01 * FU2-17)/2 +
(DRV-01*FU2-18)/2
Actual Decel Time = DRV-02 + (DRV-02 * FU2-17)/2 +
(DRV-02*FU2-18)/2
Ex) If DRV-10: 1 sec, FU2-17: 40%, FU2-18: 20%,
Actual Accel Time = 1 sec + (1sec*0.4)/2 + (1sec*0.2)/2
= 1.3 sec
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
17
40
40
18
40
40
Max. Freq./2
Time
FU2-17
FU2-18
Linear
101
Chapter 6 - Parameter Description [FU2]
FU2-19: Input/Output Phase Loss Protection (Bit
Set)
FU2? Trip select
19
00
Factory Default:
00
This function is used to cut the inverter output off in case
of phase loss in either input power or inverter output.
FU2-19 [Phase Loss Protection Select]
Setting Range
FU2-19
2
bit 1
bit
nd
st
0
0
00
Phase loss protection does not work
0
1
01
Protect inverter from output phase loss
1
0
10
Protect inverter from input phase loss
Protect inverter from input and output
1
1
11
phase loss
Related Functions:
FU2-22 to FU2-25 [Speed Search]

FU2-20: Power ON Start Selection

FU2?Power-on run
20
--- No ---
Factory Default:
No
If FUN-20 is set to ' No' , restart the inverter by cycling the
FX or RX terminal to CM terminal after power has been
restored.
If FUN-20 is set to ' Yes' , the inverter will restart after
power is restored. If the motor is rotating by inertia at the
time power is restored, the inverter may trip. To avoid
this trip, use ' Speed Search' function by setting FU2-22
to ' 1xxx' .
19
00
00
Description
20
0
0