Basic Wiring - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

1.6 Basic Wiring

Main Power
Circuit
MCCB
(Option)
φ
3
230/460V
50/60Hz
Forward Run/Stop
Reverse Run/Stop
Inverter Disable
Fault Reset
Jog
Multi-function Input 1
Multi-function Input 2
Multi-function Input 3
Common Terminal
Potentiometer
(1 kohm, 1/2W)
Speed signal Input
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
4
DC Bus Choke (Optional)
DC Bus Choke
MC
P1/
1
R
L1
S
T
G ( )
FX
RX
BX
RST
JOG
P1
Factory Setting:
P2
' Speed-L'
' Speed-M'
P3
' Speed-H'
CM
Shield
Power supply for
VR
speed signal:
+ 12V, 10mA
Speed signal input:
V1
0 ~ 10V
Speed signal input:
I
4 ~20mA (250ohm)
Common for
5G
VR, V1, I
3
Note)
Main Circuit Terminals
Control Circuit Terminals.
1. The terminal configuration varies depend on the model number. Please refer to the ' 1.7 Power terminals' .
2. Analog output voltage is adjustable up to 12V.
3. Analog speed command may be set by Voltage, Current or both.
4. The Common Busbar between
P1/L1
5. 1 ~ 10 HP inverters have built-in braking circuit. Braking resistors are only included for 1 ~ 5HP inverters.
15~30HP inverters have built-in DB unit.
Dynamic
Braking Unit
(Optional)
DB Unit(Optional)
DB Resistor
P N B1 B2
1
P2/
N
1
U
L2
V
W
FM
5G
(N.O.) 30 A
Fault output relay
less than AC250V, 1A
30 C
less than DC30V, 1A
(N.C.) 30 B
Multi-function output relay1
AXA
less than AC250V, 1A
less than DC30V, 1A
AXC
Factory setting: ' Run'
and
P2/L2
must be removed before installing DC Reactor.
15 ~ 100 HP inverters need optional braking unit and resistor.
13
Chapter 1 – Installation
5
DB Resistor
MOTOR
+
FM
Output Frequency Meter
2
(0~10V Linear)
Control Circuit