Chapter 6 - Parameter Description [FU2]

FU2-69: Accel/Decel Change Frequency

FU2?Acc/Dec ch F
69
0.00 Hz
Factory Default:
0.00 Hz
This function is used to change Accel/Decel ramp at a
certain frequency. This is useful in textile machine
application.
Note: If the multi- function input terminal (I/O-12 ~ I/O-14)
is set to ' XCEL-L' , XCEL-M' , or XCEL-H' , The Multi-
Accel/Decel Time (I/O-25 ~ I/O-38) has the priority.
Max. Frequency
Output Frequency
DRV-01 [AccTime]
I/O-25 [Acc Time1]
FX
[Accel/Decel Change Operation]
FU2-70: Reference Frequency for Accel/Decel
FU2?Acc/Dec freq
70
Max freq
Factory Default:
Max freq
This is the reference frequency for acceleration and
deceleration. If a decided Accel/Decel time from a
frequency to a target frequency is required, set this value
to ' Delta freq' .
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
69
0
0
Accel/Decel
Change
Frequency
DRV-02 [DecTime]
I/O-26 [Dec Time1]
70
0
0
114
Setting Range
LCD
7-Seg
The Accel/Decel time is the time that
0
takes to reach the maximum
Max freq
frequency from 0 Hz.
The Accel/Decel time is the time that
takes to reach a target frequency
1
Delta freq
from a frequency (currently operating
frequency).
Related Functions:
DRV-01, DRV-02 [Accel/Decel Time]
FU2-71 [Accel/Decel Time Scale]
I/O-25 ~ I/O-38 [1

FU2-71: Accel/Decel Time Scale

FU2? Time scale
71
0.1 sec
Factory Default:
0.1 sec
This is used to change the time scale.
Related Functions:
DRV-01, DRV-02 [Accel/Decel Time]
FU2-70 [Reference Freq. for Accel/Decel]
I/O-25 ~ I/O-38 [1
Setting Range
LCD
7-Seg
The Accel/Decel time is changed by 0.01
0
second. The maximum setting range is
0.01 sec
600 seconds.
The Accel/Decel time is changed by 0.1
1
second. The maximum setting range is
0.1 sec
6000 seconds.
The Accel/Decel time is changed by 1
2
second. The maximum setting range is
1 sec
60000 seconds.

FU2-72: Power On Display

FU2?PowerOn disp
72
0
Factory Default:
0
This code selects the parameter to be displayed first on
keypad (DRV-00) when the power is turned on.
Description
~ 7
Accel/Decel Time]
st
th
71
1
0.1
~ 7
Accel/Decel Time]
st
th
Description
72
0
0