Chapter 5 - Parameter Description [I/O]
6.4 Input/Output Group [I/O]

I/O-00: Jump to Desired Code #

I/O?
Jump code
00
1
Factory Default:
1
Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.
I/O-01 ~ I/O-05: Analog Voltage Input (V1) Signal
Adjustment
This is used to adjust the analog voltage input signal
when the frequency is referenced by the control terminal
' V1' . This function is applied when DRV-04 is set to ' V1'
or ' V1+I' . Reference frequency versus Analog voltage
input curve can be made by four parameters of I/O-02 ~
I/O-04.
I/O? V1 filter
01
10 ms
Factory Default:
10 ms
This is the filtering time constant for V1 signal input.
Increase this value if the V1 signal is affected by noise
causing unstable operation of the inverter. Increasing
this value makes response time slower.
I/O? V1 volt x1
02
0.00 V
Factory Default:
0.00 V
This is the minimum voltage of the V1 input at which
inverter outputs minimum frequency.
I/O? V1 freq y1
03
0.00 Hz
Factory Default:
0.00 Hz
This is the inverter output minimum frequency when
there is the minimum voltage (I/O-02) on the V1 terminal.
In torque mode, the display is changed to [%].
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
01
10
10
02
0.00
0.00
03
0.00
0.00
118
I/O? V1 volt x2
04
0.00 V
Factory Default:
10.00 V
This is the maximum voltage of the V1 input at which
inverter outputs maximum frequency.
I/O? V1 freq y2
05
60.00 Hz
Factory Default:
60.00 Hz
This is the inverter output maximum frequency when
there is the maximum voltage (I/O-03) on the V1 terminal.
In torque mode, the display is changed to [%].
Setting FU2-39 [Control mode select] to Vector_Torque
or Sensorless_T, the setting value is changed to Torque
value as below.
Code
Factory Default
I/O-02
0 [V]
I/O-03
0 [%]
I/O-04
10 [V]
I/O-05
100 [%]
Reference Frequency
I/O-05
I/O-03
I/O-02
[Reference Frequency vs. Analog Voltage Input, V1 (0 to 10V)]
Related Functions:
DRV-04 [Frequency Mode]
FU1-20 [Maximum Frequency]
I/O-06 ~ I/O-10: Analog Current Input (I) Signal
Adjustment
This is used to adjust the analog current input signal
when the terminal ' I' references the frequency. This
function is applied when DRV-04 is set to ' V1' or V1+I' .
Reference frequency versus Analog current input curve
can be made by four parameters of I/O-07 ~ I/O-10.
04
10.00
10.00
05
60.00
60.00
Setting Range
0 ~ 10 [V]
0 ~ 150[%]
0 ~ 10 [V]
0 ~ 150[%]
Analog Voltage
Input (V1)
I/O-04