I/O-11: Criteria For Analog Input Signal Loss - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

I/O?
I filter
06
10 ms
Factory Default:
10 ms
This is the filtering time constant for ' I' signal input. If the
' I' signal is affected by noise causing unstable operation
of the inverter, increase this value. Increasing this value
makes response time slower.
I/O?
I curr x1
07
4.00 mA
Factory Default:
4.00 mA
This is the minimum current of the ' I' input at which
inverter outputs minimum frequency.
I/O?
I freq y1
08
0.00 Hz
Factory Default:
0.00 Hz
This is the inverter output minimum frequency when
there is minimum current (I/O-07) on the ' I' terminal. In
torque mode, the display is changed to [%].
I/O?
I curr x2
09
20.00 mA
Factory Default:
20.00 mA
This is the maximum current of the ' I' input at which
inverter outputs maximum frequency.
I/O?
I freq y2
10
60.00 Hz
Factory Default:
60.00 Hz
This is the inverter output maximum frequency when
there is the maximum current (I/O-09) on the ' I' terminal.
In torque mode, the display is changed to [%].
Setting FU2-39 [Control mode select] to Vector_Torque
or Sensorless_T, the setting value is changed to Torque
value as below;
Code
Default
Setting
I/O-07
4 [mA]
0 ~ 20[mA]
I/O-08
0 [%]
0 ~ 150[%]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
06
10
10
07
4.00
4.00
08
0.00
0.00
09
20.00
20.00
10
60.00
60.00
Code
Default
Setting
I/O-09
20[mA]
0 ~ 20[mA]
I/O-10
100[%] 0 ~ 150[%]
119
Chapter 6 - Parameter Description [I/O]
Reference Frequency
I/O-10
I/O-08
I/O-07
[Reference Frequency vs. Analog Current Input, I (4 to 20mA)]
Related Functions:
DRV-04 [Frequency Mode]
FU1-20 [Maximum Frequency]

I/O-11: Criteria for Analog Input Signal Loss

I/O? Wire broken
11
None
Factory Default:
None
This is to set the criteria for analog input signal loss
when DRV-04 [Frequency Mode] is set to ' V1' , ' I' or
' V1+I' . Following table shows the setting value.
Setting Range
LCD
7-Seg
0
None
Does not check the analog input signal.
The inverter determines that the frequency
reference is lost when the analog input
1
half of x1
signal is less than half of the minimum
value (I/O-02 or I/O-07).
The inverter determines that the frequency
reference is lost when the analog input
2
below x1
signal is less than the minimum value (I/O-
02 or I/O-07).
When the analog input signal is lost, inverter displays the
following table.
Setting
LCD 7-Seg
Loss of frequency reference from Option Board
LOP
PL
(DPRAM time out)
Loss of frequency reference from Option Board
LOR
RL
(Communication fault)
VL
LOV
Loss of analog input signal, V1
IL
LOI
Loss of analog input signal, I
Loss of frequency reference from Sub-Board, V2 or
LOX
XL
ENC
Related Functions: I/O-48 [Lost command] selects the
operation after determining the loss of frequency
reference.