Drive Group [Drv]; Chapter 5 - Parameter List - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

CHAPTER 5 -
PARAMETER LIST

5.1 Drive Group [DRV]

Code
Description
Command Frequency or
Command Torque
(Output Frequency/
Torque during motor run,
DRV-00
11
Reference Frequency/
Torque during motor
stop)
Output Current (LCD)
DRV-01 Acceleration Time
DRV-02 Deceleration Time
Drive Mode
DRV-03
(Run/Stop Method)
Frequency Mode or
Torque Mode
DRV-04
(Frequency/Torque
setting Method)
DRV-05 Step Frequency 1
DRV-06 Step Frequency 2
DRV-07 Step Frequency 3
DRV-08 Output Current
DRV-09 Motor Speed
DRV-10 DC link Voltage
DRV-11 User Display Selection
DRV-12 Fault Display
DRV-13 Motor Direction Set
Target/Output Frequency
DRV-14
Display
Reference/Feedback
DRV-15
12
Frequency Display
DRV-16 Speed Unit Selection
DRV-20 FU1 Group Selection
DRV-21 FU2 Group Selection
DRV-22 I/O Group Selection
DRV-23
13
EXT Group Selection
11
The speed unit is changed to [%] when FU2-39 is set to ' Sensorless_T' or ' Vector_TRQ' .
12
Code DRV-15 appears only when FU2-47 is set to ' Yes' .
13
Code DRV-23 through DRV-24 appears only when a Sub-Board or an Option Board is installed.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Keypad Display
LCD
7-Segment
Cmd. freq
F or r
or
(DRV-13)
Cmd. Trq
Acc. time
01
Dec. time
02
Drive mode
03
Freq mode
04
or
Torque mode
Step freq-1
05
Step freq-2
06
Step freq-3
07
Current
08
Speed
09
DC link Vtg
10
User disp
11
Fault
12
Not displayed in
13
LCD keypad
Tar/Out Freq.
14
Ref/Fbk Freq.
15
Hz/Rpm Disp
16
Not displayed in
20
LCD keypad
21
22
23
56
Setting Range
LCD
7-Segment
0 to FU1-20 (Max. freq)
0 to 6000
0 to 6000
Keypad
0
Fx/Rx -1
1
Fx/Rx -2
2
Keypad-1
0
Keypad-2
1
V1
2
I
3
V1+I
4
0 to FU1-20
(0 to Max. freq)
Load Current in RMS
Motor Speed in rpm
DC Link Voltage inside inverter
Selected in FU2-73 (User Disp)
-
-
0 [Forward]
Not available
1 [reverse]
-
-
-
-
Hz disp
0
Rpm disp
1
Not available
Press
[PROG/ENT]
key
Adj.
Factory
During
Units
Page
Default
Run
0.01
0.00 [Hz]
Yes
79
0.1
20.0 [sec]
Yes
80
0.1
30.0 [sec]
Yes
81
-
Fx/Rx -1
No
81
-
Keypad-1
No
82
10.00 [Hz]
0.01
20.00 [Hz]
Yes
83
30.00 [Hz]
-
[A]
-
84
-
[rpm]
-
84
-
[V]
-
84
-
-
-
84
None
-
-
84
nOn
-
0
Yes
85
-
0.00 [Hz]
Yes
85
-
0.00 [Hz]
Yes
85
-
-
Yes
85
85
85
-
1
Yes
85
85

Hide quick links: