LG SV-iS5 Instruction Manual page 132

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

Chapter 6 - Parameter Description [I/O]
I/O
Run/Stop
A
Id
We
[Spd/Trq]
Speed or Torque mode select in Vector control.
Disabled in Sensorless vector
[ASR P/PI]
P or PI control select in Vector_SPD control.
Disabled in Sensorless vector
I/O-15: Terminal Input Status
I/O-16: Terminal Output Status
I/O?
In status
15
000000000
Factory Default:
000000000
This code displays the input status of control terminals.
Terminals P4, P5, P6 and Q1, Q2, Q3 are provided on
optional Sub-Board.
[LCD Keypad Display]
Input
JOG FX
RX
Terminals Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
OFF
0
0
0
status
ON status
1
1
1
[7-Segment Keypad Display]
The ' JOG' terminal is not displayed on 7-Segment keypad.
ON status
OFF status
FX RX P6 P5 P4 P3 P2 P1
This code displays the output status of control terminals.
I/O? Out status
16
0000
Factory Default:
0000
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
A: Pre-excitating
15
0000
P6
P5
P4
P3
P2
P1
0
0
0
0
0
0
1
1
1
1
1
1
16
0000
[LCD Keypad Display]
Output
AXA-AXC
Terminals
Bit 3
OFF status
0
ON status
1
[7-Segment Keypad Display]
The ' JOG' terminal is not displayed on 7-Segment keypad.
ON status
OFF status
I/O-17: Filtering Time Constant for Multi-function
Input Terminals
I/O?Ti Filt Num
17
15
Factory Default:
15
This is the response time constant for terminal inputs
(JOG, FX, RX, P3, P2, P1, RST, BX). This is useful
where there is a potential for noise. The response time is
determined by ' Filtering time constant * 0.5msec' .
I/O-20: Jog Frequency
I/O?
Jog freq
20
10.00 Hz
Factory Default:
10.00 Hz
This code sets the jog frequenc y. See [Speed-L, Speed-
M, Speed-H] in I/O-12 ~ I/O-14.
I/O-21~24: Step Frequency 4, 5, 6, 7
I/O-85~92: Step Frequency 8, 9, 10, 11, 12... 15
I/O? Step freq-4
21
40.00 Hz
Factory Default:
40.00 Hz
I/O? Step freq-7
24
30.00 Hz
Factory Default:
30.00 Hz
These codes set the step frequencies. These
126
Q3
Q2
Q1
Bit 2
Bit 1
Bit 0
0
0
0
1
1
1
AXA-AXC Q3 Q2 Q1
17
15
15
20
10.00
10.00
21
40.00
40.00
24
30.00
30.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents