6.6 Application Group [APP]

APP-00: Jump to desired code #
APP?
Jump code
00
1
Factory Default:
1
Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.

APP-01: Application Mode Selection

APP?
App. mode
01
None
Factory Default:
None
This code sets the application mode.
Setting Range
LCD
7-Seg
0
None
Application mode is not selected.
Traverse mode is selected in application
Traverse
1
group. Related functions (APP-02~07)
are displayed.
MMC (Multi-Motor Control) mode is
MMC
2
selected in application group. Related
functions (APP-08~31) are displayed.
DRAW mode is selected in application
DRAW
3
group. Related functions (APP-32~33)
are displayed.
[Traverse]: This is a mechanism to wind thread to an
intended shape on a reel with a rotary motion and
reciprocation. Adjusting the speed of mechanical
reciprocation can make different shapes of thread reel.
The following figure shows an example. The guide
should move with low speed at the center of the reel and
fast at the edge of the reel.
Related Functions:
APP-02 to APP-07 [Traverse Parameters]
I/O-12 to I/O-14 [Multi-Function Input]
EXT-30 to EXT-32 [Multi-Function Output]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
01
0
0
Description
145
Chapter 6 - Parameter Description [APP]
Thread
Traverse
Rotary
Motion
[An example of Traverse Operat i on]
APP-03
Trv. Scr
APP-02
Trv. Amp
APP-04
Traverse Acc
[Traverse Operation Pattern]
[MMC]: The ' PID' control should be selected in FU2-47
to use this function.
♦ One inverter can control multiple motors. This function
is often used when controlling the amount and pressure
of flow in fans or pumps. Built-in PI controller controls a
main motor after receiving process control value and
keeps the control value constant by connecting auxiliary
motors to commercial line when needed.
♦ In case that flow amount or flow pressure is beyond or
below the reference so the main drive cannot control by
itself, auxiliary motors are automatically turned on/off.
Maximum four (Q1~3 and Aux. output) auxiliary motors
can be run. Each Starting and Stop Frequency should
be set to four auxiliary motors.
♦ Auto Change can be selected to automatically switch
the order of the running motors for keeping motor run-
time constant. Set mode ' 1' for automatic changing of
auxiliary motors only and set mode ' 2' for automatic
changing of all motors including main motor. For m ode
' 2' , external sequence (Refer to APP-26) should be
configured.
Traverse
Thread
Reciprocation
(Constant
(Mechanical)
Speed)
APP-06
Offset-High
Reference
Speed
APP-07
Offset-Low
APP-05
Traverse Dec