Chapter 4. FUNCTION BLOCK
4.4 Error code on the function block
This shows the errors on the output variable "STAT" of variables and the resolutions in accordance with them.
STAT
Local/
No.
Remote
0
Operating with no fault
The base location number is exceeding the proper
1
setting range
2
H/W error of the base
The slot location number is exceeding the proper
3
setting range
4
The high speed counter module on the slot is empty
Local
The module loaded isn't the high speed counter
5
module
6
The channel number is exceeding the proper range
7
H/W error of the high speed counter module
8
The high speed counter module's shared memory
error
9
The available channels are not specified
128
H/W error of the communication module for remote
The base location number is exceeding the proper
129
setting range
The slot location number is exceeding the proper
131
setting range
The module loaded isn't the high speed counter
Remote
133
module
135
H/W error of the high speed counter module
136
The high speed counter module's shared memory
error
137
The available channels are not specified
Descriptions
4 - 12
Resolutions
Correct the number in accordance with the proper range(See
Section 4.2)
Contact the service station.
Set the right number to the slot mounting the high speed
counter module.
Mount the high speed counter module to the specified slot
Mount the high speed counter module to the specified slot
Specify the available channel correctly
Contact the service station.
Contact the service station.
Make a correct specification of the available channel on the
initialization function block
See the manual for the remote communication module
Corsets the number in accordance with the proper range(See
Section 4.2)
Set the right number to the slot mounting the high speed
counter module
Mount the high speed counter module to the specified slot
Contact the service station.
Contact the service station.
Make a correct specification of the available channel on the
initialization function block
-