Behavior at CPU-Master-STOP

Introduction
The 1STEP 5V/204kHz detects the CPU-master STOP. It responds by canceling the current
positioning operation.
Exiting the CPU-Master-STOP Status
ET 200 S Station
Without reassigning the parameters of the
ET 200 station
With reassignment of the parameters of the
ET 200 station
Parameter Reassignment at the ET 200S Station
A new parameter assignment of the ET 200S station by means of your CPU/ DP master
takes place:
● Upon power on of the CPU/DP master
● Upon power on of the IM 151/IM 151 FO
● After failure of the DP transmission
● After loading an altered parameter assignment or configuration of the ET 200S station
● When the 1STEP 5V/204kHz is inserted
● Upon power on or inserting of the appropriate power module
See also
Stopping the Stepping Motor (Page 37)
Pulse Enable (Page 39)
42
into the CPU/DP master
1STEP 5V/204kHz
The feedback interface of the 1STEP 5V/204kHz
remains current.
The values changed by means of parameter
assignment job are maintained.
If a control bit was set (DIR_P, DIR_M, C_PAR)
when the CPU-Master-STOP occurred, the bits
STS_JOB and ERR_JOB are set when the
CPU-Master- STOP status is exited. Delete the
control bit. The run/parameter job is not
executed. You can then start a new search by
means of the control bit.
After the delay ramp, the pulse enable, the
RDY LED, and the SYNC status bit are deleted.
Information on previous searches and parameter
assignment jobs is reset.
If pulse enable was activated by means of the
control bit DRV_EN at the time of the
CPU-Master-STOP, the pulse enable, the RDY
LED, and the SYNC status bit are deleted after
the delay ramp.
Operating Instructions, 05/2007, A5E00124871-04
ET 200S Positioning