3.6.12
Changing the Switchover Difference (JOB 4)
Definition
Changing the switchover difference allows you to adjust the drive control to adapt to any
changes in the load and mechanical conditions.
Supply the control interface with the new switchover difference, and activate JOB 4.
The 1PosInc/Digital accepts the specified switchover difference. The switchover difference
remains valid until the parameter assignment of the 1PosInc/Digital is changed.
Effect on the MODEs
MODE
Search for Reference
Inching
Absolute Positioning
Relative Positioning
Control Signals: Change Switchover Difference
Address
Byte 4
Bytes 5 to 7
Feedback Signals: Change Switchover Difference
Address
Byte 4
See also
CPU/Master Stop and RESET State (Page 104)
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
What Happens
–
The following responses are possible:
Distance to the destination ≤ the switchover difference
•
is reached or overshot; there is an immediate reduction from rapid feed to
creep feed. In this case the distance covered in creep feed is less than
(switchover difference - switch-off difference).
Distance to the destination > the switchover difference
•
The drive is moved using rapid feed, even if it was switched over to creep
feed beforehand.
Assignment
Bits 4.7 to 4.4 :
Bit
7
6
0
1
Bit 0: JOB_REQ
Switchover difference
(linear axis: 0 to 16 777 215; rotary axis: 0...16 777 215)
Assignment
Bit 0: JOB_ACK
3.6 Functions of the 1PosInc/Digital
5
4
JOB 4 = Change the switchover
0
0
difference
1PosInc/Digital
91