External Errors
Load Voltage 2L+ Missing
Causes:
Load voltage 2L+ not present or too low at
terminal 7
What to Do:
Check the wiring and correct the short circuit.
Acknowledge the error with the EXTF_ACK control
bit.
Short circuit of the sensor supply
Causes:
Short circuit of the encoder supply made available at
terminals 6 and 10
What to Do:
Check the wiring and correct the short circuit.
Acknowledge the error with the EXTF_ACK control
bit.
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
Response of the 1PosU
The current run is halted; it is not possible to start a new run.
All 3 digital outputs are set to 0.
Feedback bit POS_ERR = 1
Feedback bit POS_DONE = 0
Feedback bit ERR_2L+ = 1
Generate channel-specific diagnostics
Waits for error acknowledgment EXTF_ACK
Response of the 1PosU
The current MODEs relative positioning and absolute
positioning are stopped; it is not possible to start a new run
in these MODEs.
All 3 digital outputs are set to 0.
Feedback bit POS_ERR = 1
Feedback bit POS_DONE = 0
Feedback bit ERR_ENCODER=1
Feedback bit SYNC = 0
Generate channel-specific diagnostics
Waits for error acknowledgment EXTF_ACK
Inching MODE is not affected by this error.