1PosSSI/Analog

6.3 Terminal Assignment Diagram

6.3
Terminal Assignment Diagram
Wiring rules
The wires (terminals 1 and 5, 4 and 8) must be in twisted pairs and shielded. The shield
must be supported at both ends. You use the shield contact element
(Order Number: 6ES7 390-5AA00-0AA0) as a shield support.
Terminal assignment
Table 6-2
Terminal assignment of the 1PosSSI/Analog
Terminal assignment
Connection of Relays and Contactors to the Digital Output
Note
Direct connection of inductivities (such as relays and contactors) is possible without external
circuiting.
If SIMATIC output circuits can be deactivated by additionally installed contacts (for example
relay contacts), you have to provide additional overvoltage protection devices at inductivities
(see the following example for overvoltage protection).
248
View
Connection of the SSI Encoder:
Terminals 1-8
1: D
5: /D
3: B
7: /B
2: 24 V DC
6: M
4: C
8:/C
Remarks
Connection of the Switches and the
Drive: Terminals 9-16
Data from the SSI
9: IN0
encoder
13: IN1
Unused terminals
14: IN2
10: 24 VDC
Power supply for
12: QV+
SSI encoder
16: M
SSI clock (clock
11: OUT
line)
15: M
Operating Instructions, 05/2007, A5E00124871-04
Minus limit switch
Plus limit switch
Reducing cam; latch
signal
Encoder supply for the
switches
Analog output ± 10 or
0 V to 10 V to connect
ana
the drive
Digital output for direct
control or as a
directional signal for
the drive
ET 200S Positioning