Behavior At Cpu-Master-Stop - Siemens SIMATIC ET 200S Operating Instructions Manual

Technological functions
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

2.10

Behavior at CPU-Master-STOP

Setting the Behavior at CPU/Master-STOP
You can assign the behavior of the 1Count24V/100kHz in the event of the failure of the
parent controller.
Parameter
Turn off DO1
Continue working mode
1
DO 1 substitute a value
DO 1 keep last value
If the mode is to continue during a change from CPU-/Master-STOP to RUN (startup), the CPU/Master must not clear the
1
outputs.
Possible solution: In the part of the user program that is processed during startup, set the SW gate control bit and transfer
the values to the 1Count24V/100kHz.
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05
Status of the 1Count24V/100kHz at
CPU/Master STOP
The current mode is canceled, the gate
closed, and the digital output blocked;
comparison values 1 and 2 and the load
value are reset; the high and low limit
values, function and behavior of the digital
outputs and the integration time are handled
in accordance with the parameter
assignments.
The current mode continues, and the gate
and digital output retain their status.
The current mode is canceled, the gate
closed, and the digital output blocked;
comparison values 1 and 2 and the load
value are reset; the high and low limit
values, function and behavior of the digital
outputs and the integration time are handled
in accordance with the parameter
assignments.
When a pulse is output when the
comparison value is reached, the substitute
value is 1 only for the duration of the pulse.
The current mode is canceled, the gate
closed, and the digital output blocked;
comparison values 1 and 2 and the load
value are reset; the high and low limit
values, function and behavior of the digital
outputs and the integration time are handled
in accordance with the parameter
assignments.
1Count24V/100kHz
2.10 Behavior at CPU-Master-STOP
What Happens if
New Parameters Have Been Assigned?
The changed parameters are accepted and
take effect.
The gate is closed, the current mode is
terminated, the digital output is blocked, and
the changed parameters are accepted and
take effect.
The changed parameters are accepted and
take effect.
The changed parameters are accepted and
take effect.
109

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents