Table 5-2 Causes Of Errors For Job_Err - Siemens simatic et 200s Operating Instructions Manual

Positioning
Hide thumbs Also See for simatic et 200s:
Table of Contents

Advertisement

1PosSSI/Digital
5.6 Functions of the 1PosSSI/Digital
Causes of Errors for JOB_ERR
Table 5-2
Causes of Errors for JOB_ERR
Error Number
Meaning
21
JOB unknown
23
ERR_ENCODER is displayed
26
JOB 2 (move encoder range) cannot be initiated
because there is an active run
33
With JOB 2: Offset not in encoder range
34
Setting an Actual Value: Actual value coordinates
≥ encoder range
35
Display current values: Selection unknown
36
Latch Function: Edge selection unknown
37
Display current values: JOB 15 cannot be
activated with the latch function running.
38
Monitoring of the direction of rotation
Path difference > 65 535
232
Remedy
Permissible JOBs are:
JOB 0
JOB 1
JOB 3
JOB 4
JOB 9
JOB 10
JOB 11
JOB 15
Check the encoder wiring
Operating Instructions, 05/2007, A5E00124871-04