1PosInc/Analog
4.6 Functions of the 1PosInc/Analog
4.6.16

Changing the Deceleration Tdec (JOB 8)

Definition
By changing T
Supply the control interface with the new deceleration value and activate JOB 8.
The 1PosInc/Analog accepts the new deceleration value. The acceleration remains valid
until the parameter assignment of the 1PosInc/Analog is changed.
Figure 4-21
Effect on the MODEs
MODE
Search for Reference
Inching
Absolute Positioning
Relative Positioning
Control Signals: Changing the deceleration (T
Address
Byte 4
Bytes 5 to 7
162
(JOB 8) you can adjust the deceleration.
dec
Changing the Deceleration T
What Happens
The currently valid deceleration is replaced by the new value. The new
deceleration is immediately effective.
)
dec
Assignment
Bits 4.7 to 4.4 :
Bit
7
6
1
0
Bit 0: JOB_REQ
Deceleration T
in ms (0 to 65 535)
dec
During Deceleration
dec
5
4
JOB 8 = Changing the Deceleration T
0
0
Operating Instructions, 05/2007, A5E00124871-04