4.2 Brief Instructions on Commissioning the 1PosInc/Analog
Configured with STEP 7 via HW Config
You begin by adapting the hardware configuration to your existing ET 200S station.
1. Open the relevant project in SIMATIC Manager.
2. Call the HWConfig configuration table in your project.
3. Select "1PosInc/Analog" from the hardware catalog. The number 6ES7 138-4DJ00-0AB0
appears in the info text. Drag the entry to the slot at which you have installed your
1PosInc/Analog.
4. Double-click this number to open the "Properties for the 1PosInc/Analog" dialog box.
5. Save and compile your configuration, and download the configuration in STOP mode of
the CPU by choosing "PLC -> Download to Module".
116
On the "Addresses" tab, you will find the addresses of the slot to which you have dragged
the 1PosInc/Analog. Make a note of these addresses for subsequent programming.
On the "Parameters" tab, you will find the default settings for the 1PosInc/Analog. If you
are not connecting any limit switches to the 1PosInc/Analog, set the DI0 limit switch
minus and DI1 limit switch plus parameters to "make contact". Adapt the "DO function"
parameter to the drive interface.
Operating Instructions, 05/2007, A5E00124871-04
ET 200S Positioning