Correcting Errors On The Profibus Pa - Siemens Simatic CFU Commissioning Manual

Distributed i/o compact field unit
Hide thumbs Also See for Simatic CFU:
Table of Contents

Advertisement

Commissioning
8.8 Commissioning (online)
Additional information
● You can find additional information on parameter assignment of the field devices in the
documentation of the field device.
● You can find additional information on using SIMATIC PDM in the SIMATIC PDM help.
8.8.5

Correcting errors on the PROFIBUS PA

Check the diagnostic information of the CFU in HW Config > Module information (online) > IO
device diagnostics.
Errors and troubleshooting
Information about the LED displays of the CFU for status display can be found in section
"Diagnostics via LED displays (Page 91)".
Problem
Automatic addressing
failed
Reading out ID numbers
failed
ID number assignment
failed
PDM selected I/O differs
from HW Config for field
device at FB<x>
TAG comparison/ differ‐
ence between expected
and real TAG for field de‐
vice at FB<x>
DP slave diagnostics
available slot <x>
(Slot number in HW Con‐
fig)
88
Possible cause
Incorrect device address set (device address 2 or 3
set)
Field device is set to hardware addressing
Field device does not supply valid ID numbers. The
field device data (I/Os) cannot be recognized.
Field device does not support the set profile.
Difference between the configuration in HW Config
and the configuration in the PDM commissioning wiz‐
ard
The "Compare TAGs" function is enabled. A differ‐
ence has been detected between the name of the real
field device and the name configured in the HW Config.
Errors in the field device
Remedy
Set device address locally via PROFI‐
BUS PA
Change the device address to software
addressing, or to the correct fieldbus ad‐
dress, and restart the fieldbus connec‐
tion via the expert function.
● Read the field device data again
using the expert function.
● Use manual field device integration.
Start the commissioning wizard again
(step 5 - change configuration)
Adjust the suggested profiles in the
"Change I / O to ..." column.
● HW Config - run the function "Read
back I/O"
Apply changes
● Customizing the configuration
Start the commissioning wizard again
(step 5 - change configuration)
● Real TAG is incorrect: Adapt the real
TAG.
● Expected TAG is incorrect: Adjust in
HW Config.
Use the diagnostic functions of SIMATIC
PDM for the field device.