Operating Status Codes; Mapping Error Codes - Leroy-Somer digitax st User Manual

Sm-profibus dp-v1 solutions module for fieldbus communication
Table of Contents

Advertisement

14.2

Operating status codes

Table 14.3 PROFIBUS-DP operating status codes
Pr MM.06
>0
0
-1
-2
-3
14.3

Mapping error codes

Table 14.4 Mapping error codes
Mapping
status
0
2
3
5
30
31
32
33
104
110
111
112
113
96
Parameter
Description
Network Healthy
Indicates the number of processed cyclic messages per second.
Indicates that the PROFIBUS-DP master has established
communications with the SM-PROFIBUS DP-V1. If operating
Network Healthy,
status changes briefly to -1 and returns to 0, the slave
No Data Transfer
configuration does not match the configuration in the master
controller.
Indicates that the SM-PROFIBUS DP-V1 has initialized correctly,
Initialised
and is waiting for the PROFIBUS-DP master to initialize
communications.
Indicates that part of the SM-PROFIBUS DP-V1 initialisation
Internal Hardware
sequence was not successful. If this fault persists after a power
Failure
cycle, replace the SM-PROFIBUS DP-V1 module.
Configuration
Indicates that there is an invalid setting in the configuration
Error
parameters of the SM-PROFIBUS DP-V1 module.
Error
Description
No error detected with IN or OUT cyclic data mapping
No error detected
configuration.
Direct data
Non-cyclic data cannot be used when direct data mapping is
mapping error
enabled.
Invalid non-cyclic
An invalid non-cyclic data mode has been set in Pr MM.05.
mode
Invalid mode value The value entered in Pr MM.05 is not supported.
After expanding ranges of block mappings, too many OUT cyclic
Configuration error
data channels configured.
Total size of all OUT cyclic data mappings has exceeded the total
PPO error
size of the cyclic data.
PPO and data
More than ten cyclic OUT data channels have been selected with
format error
direct data mapping mode.
Data compression
After expanding ranges of block mappings, too many OUT cyclic
disabled with PPO
data channels configured.
A non-cyclic data mode has been mapped more than once in the
Multiple non-cyclic
IN data mapping configuration parameters
mapping error
(Pr MM.10 to Pr MM.19).
Configuration read
An error has occurred reading the IN cyclic data mapping
error
configuration parameters (Pr MM.10 to Pr MM.19) from the drive.
One or more parameters specified in the IN cyclic data mapping
Invalid source
configuration (Pr MM.10 to Pr MM.19) is outside of the allowed
parameter
range for SM-PROFIBUS DP-V1. The allowable parameter range
is from Pr 0.00 to Pr 199.99.
One or more parameters specified in the IN cyclic data mapping
Read mismatch
configuration (Pr MM.10 to Pr MM.19) cannot be used as a source
parameter for IN data. The parameter may not exist.
IN cyclic data mapping parameters (Pr MM.10 to Pr MM.19) are
Hole in IN data
not contiguous. It is not possible to have an unused parameter in
mapping
configuration
the middle of the cyclic data.
www.leroy-somer.com
SM-PROFIBUS DP-V1 User Guide
Issue : a

Hide quick links:

Advertisement

Table of Contents
loading