Table 10.9 PROFIBUS-DP operating status codes
Pr MM.06
>0
0
-1
-2
-3
If a mapping configuration error or network error is detected the drive may trip. Refer to
section 10.8 Drive trip display codes on page 58 for details about the drive trip display.
10.7

Mapping status

Table 10.10 SM-PROFIBUS DP-V1
Pr MM.49
If the SM-PROFIBUS DP-V1 operating status parameter (Pr MM.06) indicates a value of
-3, a mapping configuration error has been detected. The reason for the error is
indicated by the SM-PROFIBUS DP-V1 mapping status parameter, Pr MM.49.
When a mapping error has been corrected, re-initialize the SM-PROFIBUS DP-V1 by
setting Pr MM.32 to ON (1).
The mapping error codes are described in Table 10.11.
Table 10.11 Mapping error codes
Mapping
status
0
2
3
5
30
31
32
33
104
56
Parameter
Description
Network Healthy
Indicates the number of processed cyclic messages per second.
Indicates that the PROFIBUS-DP master has established
communications with the SM-PROFIBUS DP-V1. If operating
Network Healthy,
status changes briefly to -1 and returns to 0, the slave
No Data Transfer
configuration does not match the configuration in the master
controller.
Indicates that the SM-PROFIBUS DP-V1 has initialized correctly,
Initialised
and is waiting for the PROFIBUS-DP master to initialize
communications.
Indicates that part of the SM-PROFIBUS DP-V1 initialisation
Internal Hardware
sequence was not successful. If this fault persists after a power
Failure
cycle, replace the SM-PROFIBUS DP-V1.
Configuration
Indicates an invalid setting in the SM-PROFIBUS DP-V1
Error
configuration parameters.
Default
Range
Access
Error
No error detected
Direct data mapping error
Invalid non-cyclic mode
Invalid mode value
Configuration error
PPO error
PPO and data format error
Data compression disabled
with PPO
Multiple non-cyclic mapping
error
www.leroy-somer.com
mapping status
0
0 to 255
RO
Description
No error detected with IN or OUT cyclic data mapping
configuration.
Non-cyclic data cannot be used when direct data
mapping is enabled.
An invalid non-cyclic data mode has been selected in
Pr MM.05.
The value entered in Pr MM.05 is not supported.
After expanding ranges of block mappings, too many
OUT cyclic data channels configured.
Total size of all OUT cyclic data mappings has
exceeded the total size of the cyclic data.
More than ten cyclic OUT data channels have been
selected with direct data mapping mode.
After expanding ranges of block mappings, too many
OUT cyclic data channels configured.
A non-cyclic data mode has been mapped more than
once in the IN data mapping configuration parameters
(Pr MM.10 to Pr MM.19).
SM-PROFIBUS DP-V1 User Guide
Issue : a

Hide quick links: